Puls ML15.241 Power Supply Guia De Especificação

Página de 21
 
 
ML15.241
 
 
MiniLine 
 
24V,
 
0.63A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
3.  AC-I
NPUT
 
 
AC input 
nom. 
AC 100-240V 
 
AC input range 
 
85-264Vac continuous 
operation 
  
264–300Vac 
0.5s 
Allowed voltage L or N to earth 
max. 
300Vac 
 
Input frequency 
nom. 
50–60Hz  
±6% 
Turn-on voltage 
typ. 
59Vac 
steady-state value, see Fig. 3-1
 
Shut-down voltage 
typ. 
54Vac 
steady-state value, see Fig. 3-1
 
 
 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Input current (rms) 
typ. 
0.34A 
0.28A 
0.17A 
at 24V, 0.63A see Fig. 3-3
 
Power factor *) 
typ. 
0.52 
0.51 
0.44 
at 24V, 0.63A see Fig. 3-4
 
Crest factor **) 
typ. 
3.45 
3.53 
3.94 
at 24V, 0.63A 
Start-up delay 
typ. 
700ms 
700ms 
700ms 
see Fig. 5 2 
Rise time 
typ. 
20ms 
20ms 
24ms 
at 24V, 0.63A, see Fig. 3-2
Turn-on overshoot 
max. 
100mV 100mV 100mV 
*) 
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. 
**)  The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform. 
 
 
 
Fig. 3-1   Input voltage range 
 
Fig. 3-2   Turn-on behavior, definitions 
 
Turn-on
85V
Rated
input range
max.
500ms
V
P
OUT
4/21
IN
54V
300Vac
264V
Shut
-down
59V
 
 
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Intput
Voltage
 
 
 
Fig. 3-3   Input current vs. output load at 24V 
 
Fig. 3-4   Power factor vs. output load 
 
0.7A
0.1
0.2
0.4
0
0
0.10
0.4A
Input Current, typ.
0.5
0.20
0.3
0.6
0.25
0.15
0.05
0.30
0.35
b
c
a
a) 100Vac
b) 120Vac
c) 230Vac
Output Current
0.7A
0.1
0.2
0.3
0.5
 
0.30
0.35
0.40
0.45
0.50
0.55
Power Factor, typ.
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
Output Current
0.4
0.6
 
 
Oct. 2009 / Rev. 1.2  DS-ML15.241-EN 
All parameters are specified at 24V, 0.63A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 