Puls ML15.241 Power Supply Guia De Especificação
ML15.241
MiniLine
24V,
0.63A,
S
INGLE
P
HASE
I
NPUT
3. AC-I
NPUT
AC input
nom.
AC 100-240V
AC input range
85-264Vac continuous
operation
264–300Vac
<
0.5s
Allowed voltage L or N to earth
max.
300Vac
Input frequency
nom.
50–60Hz
±6%
Turn-on voltage
typ.
59Vac
steady-state value, see Fig. 3-1
Shut-down voltage
typ.
54Vac
steady-state value, see Fig. 3-1
AC 100V
AC 120V
AC 230V
Input current (rms)
typ.
0.34A
0.28A
0.17A
at 24V, 0.63A see Fig. 3-3
Power factor *)
typ.
0.52
0.51
0.44
at 24V, 0.63A see Fig. 3-4
Crest factor **)
typ.
3.45
3.53
3.94
at 24V, 0.63A
Start-up delay
typ.
700ms
700ms
700ms
see Fig. 5 2
Rise time
typ.
20ms
20ms
24ms
at 24V, 0.63A, see Fig. 3-2
Turn-on overshoot
max.
100mV 100mV 100mV
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range
Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
P
OUT
4/21
IN
54V
300Vac
264V
Shut
-down
59V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Voltage
Intput
Voltage
Voltage
Fig. 3-3 Input current vs. output load at 24V
Fig. 3-4 Power factor vs. output load
0.7A
0.1
0.2
0.4
0
0
0.10
0.4A
Input Current, typ.
0.5
0.20
0.3
0.6
0.25
0.15
0.05
0.30
0.35
b
c
a
a) 100Vac
b) 120Vac
c) 230Vac
b) 120Vac
c) 230Vac
Output Current
0.7A
0.1
0.2
0.3
0.5
0.30
0.35
0.40
0.45
0.50
0.55
Power Factor, typ.
a) 100Vac
b) 120Vac
c) 230Vac
b) 120Vac
c) 230Vac
b
c
a
Output Current
0.4
0.6
Oct. 2009 / Rev. 1.2 DS-ML15.241-EN
All parameters are specified at 24V, 0.63A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 0.63A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany