Puls ML15.241 Power Supply Guia De Especificação

Página de 21
 
 
ML15.241
 
 
MiniLine 
 
24V,
 
0.63A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
7.  H
OLD
-
UP 
T
IME
 
 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Hold-up Time 
typ. 
64ms 
98ms 
375ms 
at 24V, 0.32A, see Fig. 7-1
 
typ. 
31ms 
47ms 
196ms 
at 24V, 0.63A, see Fig. 7-1
Note:  At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time 
 
 
 
Fig. 7-1   Hold-up time vs. input voltage 
 
Fig. 7-2   Shut-down behavior, definitions 
 
0
25
50
125
150ms
85
120
155
190
230Vac
Input Voltage
Hold-up Time
75
100
a) 24V 0.32A typ.
b) 24V 0.32Amin.
c) 24V 0.63A typ.
d) 24V 0.63A min.
a
b
c
d
 
 
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
 
 
Oct. 2009 / Rev. 1.2  DS-ML15.241-EN 
All parameters are specified at 24V, 0.63A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 