Puls ML50.100 Power Supply Guia De Especificação
ML50.100, ML50.109
MiniLine
24V, 2.1A, S
INGLE
P
HASE
I
NPUT
Mar. 2007 / Rev. 1.0 DS-ML50.100-EN
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/20
6. I
NPUT
I
NRUSH
C
URRENT
S
URGE
A NTC limits the input inrush current after turn-on of the input voltage. The inrush current is input voltage and
ambient temperature dependent.
ambient temperature dependent.
AC 100V
AC 120V
AC 230V
Inrush
current
max.
18A
peak
23A
peak
48A
peak
40°C ambient, cold start
typ.
14A
peak
17A
peak
35A
peak
40°C ambient, cold start
Inrush
energy
typ.
0.3A
2
s 0.4A
2
s 1.5A
2
s
40°C ambient, cold start
Fig. 6-1 Input inrush current, typical behavior
Fig. 6-2 Input inrush current, zoom into the first peak
Output Voltage
Input Voltage
Input Current
Input Current
Input:
230Vac
Output:
24V, 2.1A
Ambient:
40°C
Upper curve:
Input current 20A / DIV
Middle curve:
Input voltage 1000V / DIV
Lower curve:
Output voltage 20V / DIV
Time scale:
20ms / DIV
Input:
230Vac
Output:
24V, 2.1A
Ambient: 40°C
Input current curve: 10A / DIV, 1ms / DIV
Ipeak 32.4A
The charging current into EMI suppression capacitors is
disregarded in the first microseconds after switch-on.
Input current curve: 10A / DIV, 1ms / DIV
Ipeak 32.4A
The charging current into EMI suppression capacitors is
disregarded in the first microseconds after switch-on.
7. DC-I
NPUT
DC input
nom.
DC 110-290V -25%/+30%
DC input range
min.
85-375Vdc
Continuous operation
DC input current
typ.
0.50A / 0.19A
110Vdc / 300Vdc at 24V and 2.1A
Turn-on voltage
typ.
81Vdc
Steady state value
Shut-down voltage
typ.
58Vdc
Steady state value
Fig. 7-1 Wiring for DC Input
Fus
e
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
Instructions for DC use:
a)
Use a battery or similar DC source.
b)
Connect +pole to L and – pole to N.
c)
Connect the PE terminal to a earth wire or
to the machine ground.
to the machine ground.
d)
In case the – pole of the battery is not
connected to earth, use an appropriate fuse
to protect the N terminal.
connected to earth, use an appropriate fuse
to protect the N terminal.