Puls ML50.100 Power Supply Guia De Especificação

Página de 20
 
 
 
ML50.100, ML50.109 
 
MiniLine 
 
24V, 2.1A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
Mar. 2007 / Rev. 1.0  DS-ML50.100-EN 
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
4/20 
 
6. I
NPUT 
I
NRUSH 
C
URRENT 
S
URGE
 
 
A NTC limits the input inrush current after turn-on of the input voltage. The inrush current is input voltage and 
ambient temperature dependent.  
 
AC 100V 
AC 120V 
AC 230V 
 
 Inrush 
current 
max. 
18A
peak
 23A
peak
 48A
peak
 
40°C ambient, cold start 
   
typ. 
14A
peak
 17A
peak
 35A
peak
 
40°C ambient, cold start 
 Inrush 
energy 
typ. 
0.3A
2
s 0.4A
2
s 1.5A
2
40°C ambient, cold start 
 
 
Fig. 6-1   Input inrush current, typical behavior 
 
Fig. 6-2   Input inrush current, zoom into the first peak 
 
 
Output Voltage
Input Voltage
Input Current
 
 
Input Current
 
 
 
Input:  
 
230Vac 
Output:    
24V, 2.1A 
Ambient:  
40°C 
Upper curve: 
Input current 20A / DIV 
Middle curve: 
Input voltage 1000V / DIV 
Lower curve: 
Output voltage 20V / DIV 
Time scale:  
20ms / DIV 
 
Input:  
230Vac 
Output:  
24V, 2.1A 
Ambient: 40°C 
Input current curve:  10A / DIV, 1ms / DIV 
Ipeak 32.4A 
The charging current into EMI suppression capacitors is 
disregarded in the first microseconds after switch-on. 
 
 
7. DC-I
NPUT
 
 
  DC input 
nom. 
DC 110-290V   -25%/+30% 
  DC input range 
min. 
85-375Vdc 
Continuous operation 
  DC input current 
typ. 
0.50A / 0.19A 
110Vdc / 300Vdc at 24V and 2.1A 
  Turn-on voltage 
typ. 
81Vdc 
Steady state value 
  Shut-down voltage 
typ. 
58Vdc 
Steady state value 
 
 
Fig. 7-1   Wiring for DC Input 
 
 
 
 
Fus
e
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
 
 
Instructions for DC use: 
a) 
Use a battery or similar DC source. 
b) 
Connect +pole to L and – pole to N. 
c) 
Connect the PE terminal to a earth wire or 
to the machine ground. 
d) 
In case the – pole of the battery is not 
connected to earth, use an appropriate fuse 
to protect the N terminal.