Puls ML50.100 Power Supply Guia De Especificação

Página de 20
 
 
 
ML50.100, ML50.109 
 
MiniLine 
 
24V, 2.1A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
Mar. 2007 / Rev. 1.0  DS-ML50.100-EN 
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
5/20 
 
8. H
OLD
-
UP 
T
IME
 
 
   
AC 100V 
AC 120V 
AC 230V 
 
  Hold-up Time 
typ. 
54ms 
82ms 
360ms 
1.05A, 24V, see 
Fig. 8-1
 
   
typ. 
26ms 
40ms 
180ms 
2.1A, 24V, see 
Fig. 8-1
 
 
 
Fig. 8-1   Hold-up time vs. input voltage 
 
Fig. 8-2   Shut-down behavior, definitions 
 
0
20
40
100
120ms
85
120
155
190
230Vac
Input Voltage
Hold-up Time
60
80
a) 24V 1.05A typ.
b) 24V 1.05Amin.
c) 24V 2.1A typ.
d) 24V 2.1A min.
a
b
c
d
 
 
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Intput
Voltage
 
Note:  At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time. 
 
 
9. DC-OK O
UTPUT
 
 
This feature monitors the output voltage, which is present on the output terminals. 
The signal is a source output which can feed loads up to 30mA. Loads can be a 24V relay (Rcoil < 700Ohm), a LED or 
the input of a PLC system. The relays operates  or the LED is on if output voltage exceeds the threshold level. A free-
wheeling diode (necessary when the load is a relay) is already included in the power supply. 
 
  Threshold value 
 
20V +/-4% 
  Output current 
min. 
30mA 
For typical values see 
Fig. 9-2
 
 
Output voltage 
min 
Vout – 1V 
at 30mA 
The open collector is internally linked to the positive output pole. The 
DC-OK voltage is approximately the output voltage if the output voltage 
is higher than the threshold level. 
 
 
Fig. 9-1   DC-ok wiring diagram 
 
Fig. 9-2   Output characteristic DC-OK signal 
 
+ +
MiniLine
DC
ok
-
  
-
24-28V
N L
DC-ok
Relay
LED
 
 
DC-OK Voltage
0
0
10
20
4
8
12
28V
16
20
24
40mA
25
15
5
30
35
DC-OK Current
-
DC
OK
-
+
+
ML50
V
A
Load
Test Setup