Puls ML60.241 Power Supply Guia De Especificação

Página de 22
 
 
ML60.241
 
 
MiniLine 
 
24V,
 
2.5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
22.  A
CCESSORY
 
 
DIN-Rail bracket for wall or panel mount: 
A suitable DIN-rail bracket is available on request.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
          The picture of the power supply is for representation only 
 
 
Buffer module UF20.241 
This buffer unit is a supplementary device for DC 24V power supplies. It delivers power to bridge typical mains failures 
or extends the hold-up time after turn-off of the AC power. In times when the 
power supply provides sufficient voltages, the buffer module stores energy in 
integrated electrolytic capacitors. In case of mains voltage fault, this energy is 
released again in a regulated process. One buffer module can deliver 20A which can 
also be used to support peak current demands. 
The buffer unit does not require any control wiring. It can be added in parallel to 
the load circuit at any given point. Buffer 
units can be added in parallel to increase 
the output ampacity or the hold-up time. 
DC
Buffer
Unit(s)
Power
Supply
Load
AC
+
-
 
 
 
 
 
 
 
Redundancy module MLY10.241 
MLY10
IN 1
+
-
+
-
L
N
I
I
ML60.241
L    N
Output
Input
+  +
-  -
ML60.241
L    N
Output
Input
+  +
-  -
Output
Load
+
-  -
+
-
IN 2
Voltage
Monitor
The MLY10.241 is a dual redundancy 
module, which has two diodes with 
a common cathode included. It can 
be used for various purposes. The 
most popular application is to 
configure highly reliable and true 
redundant power supply system
Another interesting applicatio
the separation of sensitive loads 
from non-sensitive loads. This avoid
the distortion of the power quality 
for the sensitive loads which can 
cause controller fail
s. 
n is 
ures.  
 
 
Sep. 2010 / Rev. 1.0  DS-ML60.241-EN 
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
16/22