Puls ML60.241 Power Supply Guia De Especificação

Página de 22
 
 
ML60.241
 
 
MiniLine 
 
24V,
 
2.5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
23.  A
PPLICATION 
N
OTES
 
23.1.  P
EAK 
C
URRENT 
C
APABILITY
 
Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current 
demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal 
output current. The same situation applies when starting a motor or switching-on a capacitive load. 
In many cases, the peak current capability also ensures a safe operation of subsequent circuit breakers. Branch circuits 
are often protected with circuit breakers or fuses. In case of a short or an overload in a branch circuit, the fuse needs a 
certain amount of over-current to trip or to blow. 
Assuming the input voltage is turned on before such an event, the built-in large sized output capacitors inside the 
power supply can deliver extra current. Discharging this capacitor causes a voltage dip on the output. The following 
two examples show typical voltage dips: 
 
 
Fig. 23-1   Peak loading with 2x the nominal 
current  for 50ms, typ. 
 
Fig. 23-2   Peak loading with 5x the nominal 
current  for 5ms, typ. 
 
Output
Voltage
17/22
10ms/DIV
Output
Current
24.5V
0A
5A
16V
 
 
24.5V
Output
Voltage
Output
Current
0A
1ms/DIV
12.5A
10.5V
 
 
Peak load 5A (resistive load) for 50ms 
Output voltage dips from 24V to 16V. 
 
Peak load 12.5A (resistive load) for 5ms 
Output voltage dips from 24V to 10.5V. 
 
23.2.  B
ACK
-
FEEDING 
L
OADS 
 
Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called 
return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force). 
This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. 
It does not matter whether the power supply is on or off. 
The maximum allowed feed-back-voltage is 35Vdc. The absorbing energy can be calculated according to the built-in 
large sized output capacitor which is specified in chapter 5. 
 
Sep. 2010 / Rev. 1.0  DS-ML60.241-EN 
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 