Puls CS3.241 Power Supply Guia De Especificação

Página de 21
 
 
 
CS3.241 
 
  CSeries 
24V, 3.3A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
September. 2007 / Rev. 1.1  DS-CS3.241-EN 
All parameters are specified at 24V, 3.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
3/21 
 
5. AC-I
NPUT
 
 
 AC 
input 
nom. 
AC 100-240V 
Wide-range- input, TN-, TT-, IT-Mains, see Fig. 5-1 
  AC input range 
 
90-264Vac 
100-120V range, continuous operation 
   
 
85-90Vac 
Short term or with output derating 
   
 
264-300Vac < 
0.5s 
 Input 
frequency 
nom. 
50 – 60Hz  
±6% 
 
 
AC 100V 
AC 120V 
AC 230V 
 
 Input 
current 
typ. 
1.5A 
1.24A 
0.68A 
At 24V, 3.3A see Fig. 5-3 
 Power 
factor 
*) 
typ. 
0.62 
0.61 
0.56 
At 24V, 3.3A see Fig. 5-1 
  Crest factor **) 
typ. 
3.1 3.2 4.0 
At 
24V, 
3.3A 
 Start-up 
delay 
typ. 
95ms 95ms 95ms 
See 
Fig. 
5-2 
 Rise 
time 
typ. 
18ms 
29ms 
56ms 
0mF, 24V, 3.3A, see Fig. 5-2 
   
typ. 
35ms 
52ms 
52ms 
3.3mF, 24V, 3.3A, see Fig. 5-2 
 Turn-on 
overshoot 
max. 
400mV 400mV 400mV 
See 
Fig. 
5-2 
 Turn-on 
voltage 
typ. 
75Vac 
75Vac 
75Vac 
Steady-state value, see Fig. 5-1 
 Shut-down 
voltage 
typ. 
58Vac 
58Vac 
58Vac 
Steady-state value, see Fig. 5-1 
*) 
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. 
**)  The crest factor is the mathematical ratio of the peak value to the RMS value of the input current waveform 
 
 
Fig. 5-1   Input voltage range 
 
Fig. 5-2   Turn-on behavior, definitions 
 
Tur
n
-on
90
Rated
input range
max.
500ms
V
IN
P
OUT
58
300Vac
264
S
hut
-down
75
 
 
Start-up
delay
Rise
Time
Ov
ershoot
- 5%
Output
Voltage
Intput
Voltage
 
 
Fig. 5-3   Input current vs. output load 
 
Fig. 5-4   Power factor vs. output load 
 
0.5
1.5
1.0
2.0
2.5
3.0 3.5A
0
0.3
0.6
0.9
1.2
1.5
1.8A
Output Current
Input
Current, typ.
(a) 100Vac
(b) 120Vac
(c) 230Vac
(a)
(b)
(c)
 
 
Power
Factor, typ.
0.5
1.0
1.5
2.0
3.5A
0.40
0.45
0.50
0.55
0.60
0.65
Output Current
2.5
3.0
(a) 100Vac
(b) 120Vac
(c)  230Vac
(a)
(b)
(c)