Puls CS3.241 Power Supply Guia De Especificação

Página de 21
 
 
 
CS3.241 
 
  CSeries 
24V, 3.3A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
September. 2007 / Rev. 1.1  DS-CS3.241-EN 
All parameters are specified at 24V, 3.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
5/21 
 
7. I
NPUT 
I
NRUSH 
C
URRENT 
S
URGE
 
 
A NTC limits the input inrush current after turn-on of the input voltage. The charging current into EMI suppression 
capacitors is disregarded in the first microseconds after switch-on. 
 
 
AC 100V 
AC 120V 
AC 230V 
 
 Inrush 
current 
max. 
24A
peak
 28A
peak
 54A
peak
 
At 40°C cold-start 
   
typ. 
20A
peak
 23A
peak
 45A
peak
 
At 40°C cold-start 
 Inrush 
energy 
typ. 
0.4A
2
s 0.5A
2
s 1.7A
2
At 40°C cold-start 
 
 
Fig. 7-1   Input inrush current, typical behavior 
 
 
 
 
Input Current
Input Voltage
Output Voltage
 
 
A: 
 
Start-up delay = Inrush delay 
Input:    
230Vac 
Output:  
24V, 3.3A 
Ambient: 25°C 
Upper curve: 
Input current 20A / DIV 
Medium curve:  Input voltage 500V / DIV 
Lower curve: 
Output voltage 20V / DIV 
Time scale:  
40ms / DIV 
 
 
 
 
8. H
OLD
-
UP 
T
IME
 
 
   
AC 100V 
AC 120V 
AC 230V 
 
  Hold-up Time 
typ. 
38ms 
60ms 
244ms 
1.65A, 24V, see 
Fig. 8-1
 
   
typ. 
19ms 
29ms 
120ms 
3.3A, 24V, see 
Fig. 8-1
 
 
 
Fig. 8-1   Hold-up time vs. input voltage 
 
Fig. 8-2   Shut-down behavior, definitions 
 
0
25
50
75
100
225ms
85
120
155
190
230Vac
Input Voltage
125
150
175
Hold-up
Time
200
24V, 3.3A, min.
24V, 3.3A, typ.
24V, 1.65A, min.
24V, 1.65A, typ.
 
 
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Intput
Voltage
 
Note:  At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is on during this time.