Puls CS3.241 Power Supply Guia De Especificação

Página de 21
 
 
 
CS3.241 
 
  CSeries 
24V, 3.3A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
September. 2007 / Rev. 1.1  DS-CS3.241-EN 
All parameters are specified at 24V, 3.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
4/21 
 
6. DC-I
NPUT
 
 
  DC input 
nom. 
DC 110-300V 
  DC input range 
min. 
88-375Vdc 
Continuous operation 
  DC input current 
typ. 
0.81A / 0.29A 
110Vdc / 300Vdc, 24V, 3.3A 
 
Output current 
max. 
2.5A 
At 24V and an input voltage between 88-110Vdc, 
see Fig. 6-2 
   
max. 
3.3A 
At 24V and an input voltage between 110-375Vdc 
  Turn-on voltage 
typ. 
103Vdc 
Steady-state value at 2.5A output load 
  Shut-down voltage 
typ. 
50Vdc 
Steady-state value at 2.5A output load 
 
Instructions for DC use: 
a) 
Use a battery or similar DC source. 
b) 
Connect + pole to L and – pole to N. 
c) 
Connect the PE terminal to a earth wire or to the machine ground. 
In case the – pole of the battery is not connected to earth, use an appropriate fuse to protect the N terminal. 
 
 
Fig. 6-1   Wiring for DC input 
 
Fig. 6-2   Output current versus input voltage, 
max. 
 
 
Fus
e
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
 
 
0
1.5
1.0
2.0
0.5
3.5A
88
110
375Vdc
DC Input Voltage
2.5
3.0
Output
Current