Puls CS3.241 Power Supply Guia De Especificação

Página de 21
 
 
 
CS3.241 
 
  CSeries 
24V, 3.3A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
September. 2007 / Rev. 1.1  DS-CS3.241-EN 
All parameters are specified at 24V, 3.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
8/21 
 
11. F
UNCTIONAL 
D
IAGRAM
 
 
 
Fig. 11-1   Functional diagram 
 
+
+
-
-
V
OUT
Input Fuse
&
Input Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC
ok
L
N
Output
Over-
Voltage
Protection
Input
Rectifier
&
NTC Inrush
Limiter
 
 
 
 
12. R
ELIABILITY
 
 
These units are extremely reliable and use only the highest quality materials. The number of critical components such 
as electrolytic capacitors has been reduced. 
   
AC 100V 
AC 120V 
AC 230V 
 
  Lifetime expectancy 
min. 
57 000h 
64 000h 
77 000h 
40°C, 24V, 3.3A 
 
 
min. 
t.b.d. t.b.d. t.b.d. 
40°C, 
24V, 
1.65A 
   
min. 
160 000h 
>15 years 
>15 years 
25°C, 24V, 3.3A 
  MTBF SN 29500, IEC 61709 
t.b.d. 
t.b.d. 
t.b.d. 
40°C, 24V, 3.3A 
 
 
t.b.d. t.b.d. t.b.d. 
25°C, 
24V, 
3.3A 
  MTBF MIL HDBK 217F 
t.b.d. 
t.b.d. 
t.b.d. 
40°C, 24V, 3.3A, Ground Benign GB40 
   
t.b.d. 
t.b.d. 
t.b.d. 
25°C, 24V, 3.3A, Ground Benign GB25 
 
The  Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the 
lifetime expectancy of the built-in electrolytic capacitors.  
Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s 
manufacturer specification. The prediction model allows a calculation of up to 15 years from date of shipment. 
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates 
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily 
represent the life of a product.