Puls CS10.241 Power Supply Guia De Especificação
CS10.241, CS10.241-S1
C–Series
24V, 10A, S
INGLE
P
HASE
I
NPUT
August 2006 / Rev. 1.1 DS-CS10.241-EN / All parameters are specified at 24V, 10A, 230Vac and 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/20
12. F
RONT
S
IDE AND
U
SER
E
LEMENTS
Fig. 12-1 Front side
Output voltage potentiometer
Open the flap to tune the output voltage.
Factory set: 24.1V
Open the flap to tune the output voltage.
Factory set: 24.1V
Output Terminals
Screw terminals
(Spring-clamp terminals on the
CS10.241-S1)
+ Positive output
- Negative (return) output
Dual pins per pole
Screw terminals
(Spring-clamp terminals on the
CS10.241-S1)
+ Positive output
- Negative (return) output
Dual pins per pole
Input Terminals
Screw terminals
(Spring-clamp terminals
on the CS10.241-S1)
N … Neutral input
L … Line (hot) input
... PE (Protective Earth) input
DC-on lamp (green)
On when the voltage on the output
terminals is > 21 V
terminals is > 21 V
13. T
ERMINALS AND
W
IRING
Type
Screw terminals (CS10.241); Spring-clamp terminals (CS10.241-S1)
Solid
wire
0.5-6mm
2
Stranded
wire
0.5-4mm
2
American wire gauge
20-10 AWG
Ferrules
allowed, but not required
Wire stripping length
7mm / 0.275inch
Screwdriver
3.5mm slotted or Pozidrive No 2 (only for screw terminals)
Recommended tightening torque
0.8Nm, 7lb.in (only for screw terminals)
Instructions:
a)
Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum.
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum.
b)
Follow national installation codes and installation regulations!
c)
Ensure that all strands of a stranded wire enter the terminal connection!
d)
Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e)
Do not use the unit without PE connection.