Puls QS5.241 Power Supply Guia De Especificação
QS5.241, QS5.241-A1
Q-Series
24V,
5A,
S
INGLE
P
HASE
I
NPUT
10. R
ELIABILITY
AC
100V
AC 120V
AC 230V
Lifetime expectancy
*)
63 000h
70 000h
89 000h
at 24V, 5A and 40°C
112 000h
116 000h
116 000h
at 24V, 2.5A and 40°C
178 000h*)
197 000h*)
252 000h*)
at 24V, 5A and 25°C
MTBF
**)
SN 29500, IEC 61709
787 000h
812 000h
831 000h
at 24V, 5A and 40°C
1 374 000h
1 409 000h
1 338 000h
at 24V, 5A and 25°C
MTBF
**)
MIL HDBK 217F
352 000h
375 000h
391 000h
at 24V, 5A and 40°C;
Ground Benign GB40
Ground Benign GB40
482 000h
509 000h
536 000h
at 24V, 5A and 25°C;
Ground Benign GB25
Ground Benign GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
Mar. 2013 / Rev. 2.2 DS-QS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/26