Puls QS5.241 Power Supply Guia De Especificação

Página de 26
 
 
QS5.241, QS5.241-A1
 
 
Q-Series 
24V,
 
5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
11.  F
UNCTIONAL 
D
IAGRAM
 
 
 
Fig. 11-1   Functional diagram 
 
 
+
+
-
-
DC-ok
contact
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC-ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Overload
LED
DC-ok
LED
Input Fuse
Input Filter
Input Rectifier
Active Transient Filter &
Inrush Current Limiter
V
OUT
L
N
 
 
 
 
12.  T
ERMINALS AND 
W
IRING
 
 
Bi-stable, quick-connect spring clamp terminals. IP20 Finger safe construction. Suitable for field- and factory 
installation. Shipped in open position. 
 
Input Output 
DC-OK-Signal 
Type 
spring-clamp terminals 
spring-clamp terminals spring-clamp 
terminals 
Solid wire 
0.5-6mm
2
 0.3-4mm
2
 0.3-4mm
2
 
Stranded wire 
0.5-4mm
2
 0.3-2.5mm
2
 0.3-2.5mm
2
 
American Wire Gauge 
20-10 AWG 
26-12 AWG 
26-12 AWG 
Wire stripping length 
10mm / 0.4inch 
6mm / 0.25inch 
6mm / 0.25inch 
Screwdriver not 
applicable 
not applicable 
not applicable 
Recommended tightening torque 
not applicable 
not applicable not 
applicable 
Pull-out force 
10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (according to UL486E) 
 
Fig. 12-1     Connecting a wire 
Instructions: 
a) Use appropriate copper cables that are designed for minimum 
operating temperatures of:  
60°C for ambient up to 45°C and  
75°C for ambient up to 60°C minimum 
90°C for ambient up to 70°C minimum. 
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal 
connection!  
d) Up to two stranded wires with the same cross section are 
permitted in one connection point (except PE wire). 
e) Do not use the unit without PE connection. 
f) Unused terminal compartments should be securely tightened. 
g) Ferrules are allowed. 
 
1. Insert the wire
2. Close the lever
To disconnect wire:
reverse the procedure
 
 
Mar. 2013 / Rev. 2.2 DS-QS5.241-EN 
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
11/26