Puls QS5.241 Power Supply Guia De Especificação

Página de 26
 
 
QS5.241, QS5.241-A1
 
 
Q-Series 
24V,
 
5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
13.  F
RONT 
S
IDE AND 
U
SER 
E
LEMENTS
 
 
 
Fig. 13-1   Front side 
 
 
 
A Input 
Terminals (Quick-connect spring-clamp terminals) 
  
N, 
Line input   
 
 
 
PE (Protective Earth) input 
 
B Output 
Terminals (Quick-connect spring-clamp terminals, two pins per pole) 
   +          Positive output  
  
–           Negative (return) output 
 
C DC-OK 
Relay 
Contact 
 (Quick-connect spring-clamp terminals) 
The DC-OK relay contact is synchronized with the DC-OK LED. 
See chapter 8 for details. 
 
D  Output voltage potentiometer  
Multi turn potentiometer; 
Open the flap to adjust the output voltage. Factory set: 24.1V 
 
E DC-OK 
LED 
(green)  
On, when the output voltage is >90% of the adjusted output voltage 
 
F Overload 
LED 
(red)  
On, when the voltage on the output terminals is <90% of the adjusted output voltage, 
or in case of a short circuit in the output. 
Input voltage is required 
Flashing, when the unit has switched off due to over-temperature. 
 
 
Indicators, LEDs 
 
Overload LED 
DC-OK LED 
DC-OK Contact 
Normal mode 
OFF 
ON 
Closed 
During BonusPower
®
  
OFF 
ON 
Closed 
Overload (V
OUT
 < 90%) 
ON 
OFF 
Open 
Output short circuit 
ON 
OFF 
Open 
Temperature Shut-down 
Intermitted 
OFF 
Open 
No input power 
OFF 
OFF 
Open 
 
Mar. 2013 / Rev. 2.2 DS-QS5.241-EN 
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 