4.  DC-I
NPUT
 
 
DC input 
nom. 
DC 110-150V 
-20%/+25% 
DC input range 
min. 
88-187Vdc 
 
DC input current 
typ. 
4.6A 
110Vdc, at 24V, 20A 
Allowed Voltage L/N to Earth 
max. 
375Vdc 
IEC 62103 
Turn-on voltage 
typ. 
74Vdc 
steady state value 
Shut-down voltage 
typ. 
69Vdc 
steady state value 
 
 
Fig. 4-1   Wiring for DC Input 
 
Instructions for DC use: 
 
+
-
Load
L
PE
+
-
Power Supply
AC
DC
Battery
N
 
 
a)  Use a battery or similar DC source. 
For other sources contact PULS 
b)  Connect +pole to L and –pole to N. 
c)  Connect the PE terminal to an earth wire or to the 
machine ground. 
 
 
5.  I
NPUT 
I
NRUSH 
C
URRENT
 
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short 
input voltage interruptions. 
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. 
 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Inrush current 
max. 
13A
peak
 13A
peak
 13A
peak
 
over entire temperature range;
mains interruptions > 750ms 
 typ. 
11A
peak
 9A
peak
 7A
peak
 
over entire temperature range;
mains interruptions > 750ms 
Inrush energy 
max. 
5A
2
s 5A
2
s 5A
2
over entire temperature range;
mains interruptions > 750ms 
Inrush delay (A) 
typ. 
400ms 
400ms 
650ms 
 
 
Fig. 5-1   Input inrush current, typical behavior 
 
 
 
Input
Current
Input Voltage
Output
Voltage
A
 
 
 
A…. Inrush 
delay 
 
Input:  
230Vac 
Output:  
24V, 20A 
Ambient: 25°C 
Upper curve: 
Input current 5A / DIV 
Middle curve: 
Input voltage 500V / DIV 
Lower curve: 
Output voltage 20V / DIV 
Time basis:  
100ms / DIV 
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN 
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
5/26