6.  O
UTPUT
 
 
Output voltage 
nom. 
24V 
 
Adjustment range 
min. 
24-28V 
guaranteed 
 max. 
30V 
****)
 
at clockwise end position of potentiometer 
Factory setting 
typ. 
24.1V  
±0.2%, at full load, cold unit 
Line regulation 
max. 
10mV 
60-300Vac 
Load regulation 
max. 
100mV 
static value, 0A Æ 20A 
Ripple and noise voltage 
max. 
100mVpp 
20Hz to 20MHz, 50Ohm 
Output current  
nom. 
20A 
continuously available at 24V, see Fig. 6-1
 nom. 
17A 
continuously 
available at 28V, see Fig. 6-1
 
nom. 30A
 *)
 
short term available BonusPower
® *)
,  
at 24V, for typical 4s, see Fig. 6-1
 
nom. 26A
 *)
 
short term available BonusPower
® *)
,  
at 28V, for typical 4s, see Fig. 6-1
Output power 
nom. 
480W 
continuously available 
 nom. 
720W 
*)
 
short term available BonusPower
® *)
 
BonusPower
® 
time typ. 
4s 
duration 
until 
the output voltage dips, see Fig. 6-2
 min. 
3.5s 
 
 max. 
4.5s 
 
BonusPower
® 
recovery time 
typ. 
7s 
overload free time to reset power manager Fig. 6-4
Overload behaviour 
 
cont. current 
  
Hiccup
PLUS
 mode
**)
 
output voltage < 20Vdc, see Fig. 6-1
Short-circuit current min. 
30A 
***)
 
 max. 
40A 
***)
 
 
max. 14A 
***)
 
average (R.M.S.) current, load impedance <10mOhm, 
see Fig. 6-3
Output capacitance 
typ. 
8 500μF 
included inside the power supply 
*)  
BonusPower®, short term power capability (up to typ. 4s) 
The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short-
term duration is hardware controlled by an output power manager. This BonusPower
®
 is repeatedly available. Detailed information 
can be found in chapter 22.1. If the power supply is loaded longer with the BonusPower
®
 than shown in the Bonus-time diagram (see 
Fig. 6-2), the max. output power is automatically reduced to 480W. If the power requirement is continuously above 480W and the 
voltage falls below approx. 20V (due to the current regulating mode at overload), the unit shuts-off and makes periodical restart 
attempts. This behaviour is called hiccup mode, which is described below. If the voltage is above 20V, the unit continuously delivers 
current. 
**)  
Hiccup
PLUS
 Mode 
At heavy overloads (when output voltage falls below 20V), the power supply delivers continuous output current for 2s. After this, the 
output is switched off for approx. 17s before a new start attempt is automatically performed. This cycle is repeated as long as the 
overload exists. If the overload has been cleared, the device will operate normally. See also Fig. 6-3.  
During the off-period a small rest voltage and rest current is present on the output. 
***) 
Discharge current of output capacitors is not included. 
****)  This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not 
guaranteed value which can be achieved. The typical value is about 28.5V. 
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN 
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
6/26