Puls QS20.241 Power Supply Guia De Especificação

Página de 26
 
 
QS20.241, QS20.241-A1, QS20.241-C1
 
 
Q-Series 
24V,
 
20A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
7.  H
OLD
-
UP 
T
IME
 
 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Hold-up Time 
typ. 
64ms 
64ms 
99ms 
at 24V, 10A, see Fig. 7-1
 
 
typ. 
32ms 
32ms 
51ms 
at 24V, 20A, see Fig. 7-1
 
 
 
Fig. 7-1   Hold-up time vs. input voltage 
 
Fig. 7-2   Shut-down behavior, definitions 
 
10
20
30
40
50
100ms
85
120
155
190
230Vac
Input Voltage
24V, 20
A, min.
60
70
80
Hold-up
Time
90
24V,
 20A
, typ
.
24V
, 10
A, m
in.
24
V, 
10
A, 
typ
.
 
 
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
 
 
 
8.  DC-OK
 
R
ELAY 
C
ONTACT
 
 
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed 
voltage from a unit connected in parallel to the power supply output. 
 
Contact closes 
As soon as the output voltage reaches the adjusted output voltage level. 
Contact opens 
As soon as the output voltage dips more than 10% below the adjusted output voltage.  
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored. 
Contact re-closes 
As soon as the output voltage exceeds 90% of the adjusted voltage. 
Contact ratings 
max 
60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A 
resistive load 
 min 
1mA 
at 
5Vdc  min. permissible load 
Isolation voltage 
 
 
Fig. 8-1   DC-ok relay contact behavior 
 
 
250ms
0.9* V
ADJ
<
1ms
10%
open
V
OUT 
= V
ADJ
open
closed
closed
>
1ms
 
 
Note:  The DC-ok feature requires that the output voltage reaches the nominal (=adjusted) level after turn-on in order to function according 
to specification. If this level cannot be achieved, the overload lamp will be on and the DC-ok contact will be open. The overload signal 
will only shut off as soon as the adjusted voltage is reached. This is an important condition to consider particularly, if the load is a 
battery, the power supply is used in parallel or the power supply is used for N+1 redundant systems. 
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN 
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
8/26