TDC-0838-000 2.4GZ OpenWay Gas Module Installation Guide - Remote Mount 
53 
 
This chapter provides the instructions to install Remote 2.4GZ OpenWay Remote Mount 
Gas Modules (Itron part number OWG-5001-501 and OWG-5002-501 with 2.5 foot cable 
and encoder) on the diaphragm gas meters where a direct mount endpoint is not possible. 
Reference the Itron Gas Endpoint Meter Compatibility List (PUB-0117-002 or the 
2.4GZ 
OpenWay Remote Mount Gas Module Meter Compatibility List
 on page 3 for compatible 
diaphragm meters.  
 
Tools and Materials Supplied By You 
 
Note  2.4GZ OpenWay Remote Mount Gas Module installation to a diaphragm 
meter may require additional tools and materials over those listed i
Installation 
Prerequisites
 on page 7. 
The following user/installer-supplied tools and materials are required to install, program, 
and check the 2.4GZ OpenWay Remote Mount Gas Module: 
•  Medium flat-blade screwdriver for band clamps. 
•  Medium flat-blade, torque-measuring screwdriver for screws to attach adapter plates 
to pipe brackets  and screws to attach endpoints to adapter plates. (Use torque 
measured 9 to 12 inch-pounds.) 
•  Medium Philips screwdriver to attach endpoints to flat surfaces 
•  Pliers to secure cable ties. 
•  Side-cutting pliers or similar tool for removing excess cable tie ends. 
•  1/4" nut driver or other blunt tool for seating endpoint tamper seals. 
•  FC200SR handheld with Endpoint-Link or Endpoint-Link Pro (version 5.3 or higher) 
for programming and checking endpoints.  
•  1" putty knife or similar tool to remove old gasket material from the meter and index 
cover. 
•  Replacement temperature compensation (TEMP COMP) meter index stickers (if 
required). 
 