SNMP/HTTP NETWORK MANAGEMENT CARD
The management card by EVER is optional and can be installed by the user. It is a device that is used to integrate the 
UPS with the Ethernet-type computer network. The network card is located in a special slot on the back wall of the 
UPS. The network card enables the user to manage the UPS from any computer in the network. This solutionis most 
often used for central power supply, orif thereisa need to manage the power supply system remotely.
The management card has the following services implemented:
- SNMP agent enables power supply management with the software progamme called SNMP manager.
- HTTP server enables the UPS parameters to be displayed and modified by using a WWW browser
NOTE! If the SNMP card is connected, communication through RS232 and USB as well as byusing 
PowerSoft Personal software are disabled.
SUPERLINE 1-1
6-11, 8-11, 10-11, 12-11
!
EPO                                                                                                                                                                                
MANUAL BYPASS
EPO (Emergency Power Off) is a mechanism that cuts off the energy supply to the receivers at the UPS output in 
extreme cases (e.g. a fire). The UPS then switches to EMERGENCY mode.
The mechanism can be activated in two ways:
- by breaking the contacts of the external EPO joint (release).
- forced from the user interface level (CONTROL 1/4 EmergencyOff).
Reactivation of the output voltage takes place only when the user deletes the failure flag indication (CONTROL 3/4 
Delete Emergency) and sets the release to inactive (standard release status) in the case of an external release. It is 
possible  to  temporarily  lock  the  EPO  function  for  the  duration  of  the  EPO  release  installation. Then,  the  person 
performing the installation may take out the EPO connector without the risk of disconnecting the supply for receivers. 
The operation may continue for a maximum of one minute from the setting of the control flag (CONTROL 2/4, EPO Off 
Time). After that time, the lock is automatically off.
The UPS is fitted with a manual switch for the BYPASS line, which enables automatic BYPASS line
switching to the output terminals of the UPS bypassing the UPS sections.
RS 232 AND USB COMMUNICATION
Superline  UPS  are  provided  with  extended  management  options.  POWERLINE  UPS  are  fitted  with  an  Rs232 
communication  port  and  PowerSoft  Personal  software,  which  are  provided  together  with  the  UPS.  It  should  be 
remembered that only one port may be used at a time and, to ensure communication, it is necessary to connect the 
UPS port to a free computer port with a connector provided. If the user would like to use an RS232 standard for 
communication, the RS232 cable should be connected to the appropriate ports prior to starting the computer and 
UPS. Then, the UPS and computer should be connected and the software should be installed as per the enclosed 
manual and the installation application's instruction. If the USB port and connector is to be used for communication, 
prior to connecting the cable, the software should be installed as per the enclosed manual and by following the 
installation application's instructions.