INSTALLATION GUIDELINES
MODEL
Apparent/active power
Primary and BYPASS
line protection
Supply system topology  
Rated current
Minimum wire size
model 6k
1P3W
SUPERLINE
Rated voltage
230V
Rated input frequency
50Hz
model 8k
SUPERLINE
model 10k
SUPERLINE
model 12k
SUPERLINE
6kVA / 4,8kW
8kVA / 6,4kW
10kVA / 8kW
12kVA / 9,6kW
OUTPUT PARAMETERS
POWER SUPPLY PARAMETERS
Switch fuse
Switch fuse
23A
31A
38A
46A
2
6 mm
10 
2
mm
10 
2
mm
10 
2
mm
40 A gG
63 A gG
80 A gG
80 A gG
40 A gG
63 A gG
80 A gG
80 A gG
Output line protection
Output system topology  
Rated current
Minimum wire size
Rated output voltage  
Switch
disconnector
1P3W
230V
21A
28A
35A
42A
2
6 mm
10 
2
mm
10 
2
mm
10 
2
mm
40 A
63 A
80 A
80 A
ENVIRONMENTAL PARAMETERS
Quantity of heat released for nominal work
conditions     
<1650 BTU
<2200 BTU
<2800 BTU
<3300 BTU
MECHANICAL PARAMETERS
Operating distance
front: > 200 mm, sides: > 100 mm, back: > 300 mm
CONNECTING THE UPS
The weight of the device should be considered when selecting the location for the installation. The UPS should be 
used  only  in  rooms  when  the  dust  level,  temperature  and  humidity  are  within  the  device's  specifications.  The 
appropriate cooling conditions must be ensured for the UPS to work correctly. For this reason, the ventilation openings 
of the UPS must be uncovered at all times, and the distance between the UPS and other objects should not be less 
than 30 cm.
The details are provided in a separate document along with the installation guidelines that are provided with 
the product.
SUPERLINE 1-1
6-11, 8-11, 10-11, 12-11