Cable routing
NOTICE
Never run low voltage (24V and less) wires like communication wires, inputs or
sensor wires in the same conduit as a high voltage (Power) wires.
When low voltage cables run parallel to high voltage cables (120/230/380 VAC or 24 VDC), place them at
a distance of at least 300 mm (12 inches) from each other to avoid electromagnetic interference.
If low voltage cables cross high voltage cables, ensure they cross at a 90° angle to minimize electromag-
netic interference.
WARNING
Do not use rigid conduits over 1 inch (25.4mm) for the KP-8IN-1REL, TP-8IN-1REL,
TR-2IN-1REL.
Grounding recommendations for the system
A correctly grounded system protects your equipment from electrical surges and spikes.
CAUTION
Each module must have its own ground connection from a common junction box.
Do not run the earth ground cable between the modules.
NOTICE
The ground resistance levels must comply with local and national electrical codes.
IMPORTANT: If outdoor connections are used, mount the enclosure as close as possible to the entry
point of the outdoor wiring.
IMPORTANT: An improper ground connection voids the system’s warranty.
Insert the rod into the ground until a few inches of the tip is left above ground level. Attach the cable to the
rod tip with an appropriate connector. Attach the other end of the cable to a breaker box or a junction box
near the main enclosure.