GSI ELECTRONICS INC. EDGERFID Manual Do Utilizador

Página de 70
WARNING
Take note that the controller is not able to show the DC current value on the
screen when a DC source is used but the electronic fusible of the relay can
protect under a DC source.
NOTICE
When tightening small terminal blocks, use a torque between 0.5N*m
(4.43lbf*in) and 0.6 N*m (5.2lbf*in) to fasten a wire gauge from 16AWG to
18AWG.
See
Technical Specifications, page
to know the resistive load, motor load, and relay ratings
according to the load used and the possible load configuration. Refer to your local building code to
determine the type and quality of cable required. A minimum voltage rating of 300V and a minimum
temperature rating of 90°C is used for the wires.
See Appendix Technical Specifications to know the resistive load, motor load, and relay ratings
according to the load used and the possible load configuration. Refer to your local building code to
determine the type and quality of cable required. A minimum voltage rating of 300V and a minimum
temperature rating of 90°C is used for the wires.
GSI Electronics recommends the use of fuse in series at the output of a relay with a circuit breaker.
Grounding
The KP-8IN-1REL, TP-8IN-1REL, TR-2IN-1REL only needs a functional Earth.
The functional Earth connector is located at J2.
WARNING
If metal rigid tubes are used, ensure they are correctly grounded.
NOTICE
When tightening the Earth terminal blocks, use a torque from 0.9N*m (7.9lbf*in) to
1.0 N*m (8.9lbf*in) to fasten a wire gauge from 12AWG to 16AWG.
22
895-00695