●  It cannot correct faults with the control process > lasting loop error. 
●  It reacts immediately to a change in the process value. 
●  It is stable. 
I Controller 
An integral-action controller (I controller) changes the manipulated variable M proportional to 
the loop error and to the time. The I controller works by delayed action. It completely 
remedies a loop error. 
In order to calculate the value of the manipulated variable at a period of time n, the time up 
until this period of time must be divided into small time slices. The loop errors at the end of 
each time slice must be added up (integrated) and they are then entered in the calculation. 
M
In
 = k
I
 × (T
S
 / T
I
) × (e
n
 + e
n-1
 + e
n-2
 + e
n-3
 + … + e
0
) = k
I
 × (T
S
 / T
I
) × e
n
 + M
In-1
 
M
In
: Manipulated variable of the I controller at the time n 
M
In-1
: Manipulated variable of the I controller at the time n-1; also called integral sum 
k
I
: Gain of the I controller 
T
S
: Sampling time, duration of a time slice 
T
I
: Integral time: by means of this time, the influence of the integral part is controlled on the 
manipulated variable, also known as integral-action time 
e
n
: Loop error at the time n 
e
n-1
: Loop error at the time n-1; etc. 
e
0
: Loop error at the beginning of the calculations 
The following picture shows a jump in process value and step response of the controller:  
 
Summary 
The I controller has the following characteristics: 
●  It sets the process value exactly to the command variable. 
●  By so doing, it tends to oscillate and is unstable. 
●  It requires more time to carry out the control action than the P controller . 
PI controller 
A PI controller reduces the loop error immediately and will eventually drive the loop error to 
zero.