Reference material 
 
5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
299
 
5.3.5.3 
Description of the individual parameters 
 
Controller 
parameters 
Portrayed in LOGO! 
Possible value 
range in the 
LOGO! 
Mn 
Manipulated variable 
at the time n 
Output of the PI controller block 
0 to 1000 
kP 
Gain of the P part 
kI 
Gain of the I part 
 
In the LOGO!, the parameter KC applies as an increase for 
the I part and the P part of the controller equally 
Should you enter KC=0, then the P part of the controller 
switches off. In this special case, k is automatically set to 1 
for the I part. 
If KC = 0: kP = 0 and kI = 1 
If KC ≠ 0: kP = kI = KC 
0.00 to 99.99 
T
S
 
Sampling time, 
duration of a time 
slice 
Fixed 
500 ms 
T
I
  
Integral time 
Parameter T
I:
 if you set this parameter to 99.59 min, then 
you switch off the I part of the controller. 
00:01 min to 
99.59 min 
e
n
 
Loop error at the 
time n; generally 
applies: 
E = SP - PV 
Refer to SP and PV 
SP 
The parameter SP is the set-value assignment w. For this 
parameter you can use the analog output of a different 
special function. 
-10000 to +20000 
PV 
PV is the process value x and is calculated as follows:  
PV = analog value on input * gain) + offset. 
You can connect the input for example by means of an 
analog input with a PT100 sensor. 
 
The gain parameter has an effect on PV 
0.0 to 10.0 
 
The offset parameter has an effect on PV 
-10000 to +20000 
 
PV is restricted by the parameters Min. and Max. 
In each case: 
10000 to +20000 
 
The Dir parameter gives the action direction of the 
controller. 
Positive means: If set value > process value then the 
process value is increased; if set value < process value 
then the process value is reduced. 
Negative means: If set value > process value then the 
process value is reduced; if set value < process value then 
the process value is increased. 
Example, heat regulation: if the set value is greater than 
the process value (room is too cold), the manipulated 
variable increases the process value. 
- or + 
Refer to the PI controllers - description of special function for more details (for example, 
switching from manual to automatic mode, parameter sets, etc.).