Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
7-6
Table 7-1 lists the maximum distances from the NAC terminal block to the last appliance 
in a Class A configuration, depending on wire gauge and current. Use Table 7-1 to 
calculate wire distances for your application if you are using Class A wiring.  
Table 7-1. Class A Wiring Distances 
Alarm 
Current @ 
24 V 
Max Distance 
w/ 18 AWG 
(0.8231 mm
2
Max Distance 
w/ 16 AWG 
(1.309 mm
2
Max Distance 
w/ 14 AWG 
(2.081 mm
2
Max Distance 
w/ 12 AWG 
(3.309 mm
2
DC 
Resistance 
0.25 A 
420 ft. (128 m) 
667 ft. (203 
m) 
1,063 ft. (324 
m) 
1,691 ft. (515 
m) 
6 Ohms 
0.50 A 
210 ft. (64 m) 
334 ft. (102 
m) 
532 ft. (162 m)
845 ft. (258 m) 
3 Ohms 
0.75 A 
140 ft. (43 m) 
222 ft. (68 m)  354 ft. (108 m)
564 ft. (172 m) 
2 Ohms 
1 A 
105 ft. (32 m) 
167 ft. (51 m) 
266 ft. (81 m) 
423 ft. (129 m) 
1.5 Ohms 
1.25 A 
84 ft. (26 m) 
133 ft. (41 m) 
213 ft. (65 m) 
338 ft. (103 m) 
1.2 Ohms 
1.50 A 
70 ft. (21 m) 
111 ft. (34 m) 
177 ft. (54 m) 
282 ft. (86 m) 
1 Ohm 
1.75 A 
60 ft. (18 m) 
95 ft. (29 m) 
152 ft. (46 m) 
242 ft. (74 m) 
0.86 Ohm 
2 A 
53 ft. (16 m) 
83 ft. (25 m) 
133 ft. (41 m) 
211 ft. (64 m) 
0.75 Ohm 
2.25 A 
47 ft. (14 m) 
74 ft. (23 m) 
118 ft. (36 m) 
188 ft. (57 m) 
0.67 Ohm 
2.50 A 
42 ft. (13 m) 
67 ft. (20 m) 
106 ft. (32 m) 
169 ft. (51 m) 
0.60 Ohm 
2.75 A 
38 ft. (12 m) 
61 ft. (19 m) 
97 ft. (30 m) 
154 ft. (47 m) 
0.55 Ohm 
3 A 
35 ft. (11 m) 
56 ft. (17 m) 
89 ft. (27 m) 
141 ft. (43 m) 
0.50 Ohm 
 
Notes: 
•  Max Distance = distance from SPS/RPS to last appliance. 
•  This table is calculated at 49 degrees Centigrade (120 degrees 
Fahrenheit). If you are installing in locations that could be exposed to 
higher temperatures, refer to NEC Tables 7 and 8 in NFPA code, or 
applicable local standard. 
•  Distances are based on a 3 V drop, and take into account the worst-case 
panel output voltage.  These distances are worst case to allow for one 
single load at the furthest point. 
•  If circuit integrity wire is used instead of housing cable in a fire-rated 
enclosure, reduce wiring distances by 38 feet (12 m) for every 10 feet (3 
m) of potential exposure. 
•  For other wire gauges (e.g. 4 mm
2
) multiply the distance specified for the 
nearest wire size by the ratio of the wire area, e.g. for 3A on 4 mm
look 
up 3A on 12AWG (3.3 mm
2
) and multiply the resulting 43m x 4.0/3.3 = 
52m. 
 
Continued on next page 
Class A NAC  
Wiring Table