Table 7-2 lists the maximum distances from the NAC terminal block to the last appliance 
in a Class B configuration, depending on wire gauge and current. Use Table 7-2 to 
calculate wire distances for your application if you are using Class B wiring.  
 
             Table 7-2. Class B Wiring Distances 
Alarm 
Current @ 
24 V 
Max Distance 
w/ 18 AWG 
(0.8231 mm
2
Max Distance 
w/ 16 AWG 
(1.309 mm
2
Max Distance 
w/ 14 AWG 
(2.081 mm
2
Max Distance w/ 
12 AWG 
(3.309 mm
2
DC 
Resistance 
0.25 A 
840 ft. (256 m) 
1,335 ft. (407 m)  2,126 ft. (648 m)  3,382 ft. (1,031 m) 
12 Ohms 
0.50 A 
420 ft. (128 m) 
667 ft. (203 m) 
1,063 ft. (324 m) 
1,691 ft. (515 m) 
6 Ohms 
0.75 A 
280 ft. (85 m) 
445 ft. (136 m) 
709 ft. (216 m) 
1,127 ft. (344 m) 
4 Ohms 
1 A 
210 ft. (64 m) 
334 ft. (102 m) 
532 ft. (162 m) 
845 ft. (258 m) 
3 Ohms 
1.25 A 
168 ft. (51 m) 
267 ft. (81 m) 
425 ft. (130 m) 
676 ft. (206 m) 
2.4 Ohms 
1.50 A 
140 ft. (43 m) 
222 ft. (68 m) 
354 ft. (108 m) 
564 ft. (172 m) 
2 Ohms 
1.75 A 
120 ft. (37 m) 
191 ft. (58 m) 
304 ft. (93 m) 
483 ft. (147 m) 
1.71 Ohms 
2 A 
105 ft. (32 m) 
167 ft. (51 m) 
266 ft. (81 m) 
423 ft. (129 m) 
1.5 Ohms 
2.25 A 
93 ft. (28 m) 
148 ft. (45 m) 
236 ft. (72 m) 
376 ft. (115 m) 
1.33 Ohms 
2.50 A 
84 ft. (26 m) 
133 ft. (41 m) 
213 ft. (65 m) 
338 ft. (103 m) 
1.2 Ohms 
2.75 A 
76 ft. (23 m) 
121 ft. (37 m) 
193 ft. (59 m) 
307 ft. (94 m) 
1.09 Ohms 
3 A 
70 ft. (21 m) 
111 ft. (34 m) 
177 ft. (54 m) 
282 ft. (86 m) 
1 Ohm 
 
Notes: 
•  Max Distance = distance from SPS or RPS to last appliance. 
•  This table is calculated at 49 degrees Centigrade (120 degrees 
Fahrenheit). If you are installing in locations that could be exposed to 
higher temperatures, refer to NEC Table 7 and 8 in NFPA code, or 
applicable local standard. 
•  Distances are based on a 3 V drop, and take into account the worst-case 
panel output voltage.  These distances are worst case to allow for one 
single load at the furthest point. 
•  If circuit integrity wire is used instead of housing cable in a fire rated 
enclosure, reduce wiring distances by 38 feet (12 m) for every 10 feet (3 
m) of potential exposure. 
•  For other wire gauges (e.g. 4 mm
2
) multiply the distance specified for the 
nearest wire size by the ratio of the wire area, e.g. for 3A on 4 mm
look 
up 3A on 12AWG (3.3 mm
2
) and multiply the resulting 86m x 4.0/3.3 = 
104m. 
 
 
Continued on next page 
 
 
 
Power Supply Wiring Distances, 
Continued 
Class B NAC  
Wiring Table