The panel, battery-backed, unregulated dc bulk power is available from the SPS via the 
NAC and the 24V Aux power terminals (1 pair only, ref fig 7-4).  NACs not configured 
as switched outputs may be configured as auxiliary power point type in the 4100 
Programmer.  All of these are power-limited. 
 
Review the following guidelines before using the SPS for auxiliary power.  
 
•  Voltage rating: 24 VDC (nominal), 2 V P-P ripple (maximum). 
•  The total auxiliary current available for non-alarm is 5 A. The total current available 
for the entire SPS is 9 A, including NAC, auxiliary, and card power.  
•  All wiring is 0.75 mm
2
 to 4 mm
2
.  
•  All SPS powered field wiring requires a ferrite bead (ref fig 7.1). 
•  All wiring that leaves the building requires overvoltage protection. Install 
module  
2081-9044 wherever wire enters or exits the building. A maximum of four 2081-
9044 Modules may be connected to one channel. 
•  When a NAC is configured as an auxiliary power circuit, no end-of-line resistor 
is used. 
•  External wiring is not supervised unless an end-of-line relay is wired, coil to 
auxiliary power, and Normally Open contacts are monitored by a system power 
point. Relay current must be considered as part of the load. 
•  Programming is required for the dedicated Auxiliary Power output (TB3). 
•  The following devices may be connected to the 2 A Auxiliary Power: 
2088-series relays and door holders 
2098-series four-wire smoke detectors 
2190-series monitor and signal ZAMs 
- 4090-series 
IDNet 
ZAMs 
4098-series four-wire smoke detectors and duct detectors 
- 2190-9039 
Printer 
4190-9050/9051 4-20 mA ZAMs 
- 4603-9101 
LCD 
Annunciator 
•  The Auxiliary Power output is rated at 2 A dc. 
•  Where multiple loads are to be connected with individual protection, a Fused DC 
Distribution board may be fitted directly to the SPS bracket adjacent to TB3. 
 
Continued on next page 
 
SPS Auxiliary Power Wiring 
Overview 
Guidelines