Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
7-9
 
 
The SPS can connect to auxiliary power appliances via the dedicated auxiliary power tap 
(TB3). If more power is needed, any of the three NAC outputs can be used for EMC 
auxiliary power.
 
 
B+
0V 24V
AUX POWER
B- A+ A-
B+ B- A+ A-
B+ B- A+ A-
AUXILIARY
POWER
AUXILIARY
POWER
AUXILIARY
POWER
AUXILIARY
POWER
 
 
 
 
 
 
Figure 7-4. Auxiliary Power Wiring 
 
SPS Auxiliary Power Wiring, 
Continued
 
Wiring
 
•  Maximum per NAC: 3 A 
•  Maximum per Auxiliary Power output: 2 A 
•  Class A wiring is possible only if 4090-9117 Power Isolators are used. 
•  EMC compliant systems require ferrite beads. Use kit SX0005. 
 
 
Devices
Primary
Return
TB1
TB2
24V
0V
TB1
TB2
To SPS/ 
RPS  
 
Class A aux power wiring requires the use 
of 4090-9117 IDNet Power Isolators, as 
shown above. 
4090-9117 
ISOLATOR 
4090-9117 
ISOLATOR 
SPS 
TB2 
TB3 
Dedicated auxiliary 
power screw terminal 
(configured in the 
Programmer) 
NAC points must be 
reconfigured as 
auxiliary power 
output points in the 
programmer 
0.75 mm
2
 to 4 mm
2
 
 
 
0.75 mm
2
 to 4 mm
2
 
Ferrite bead 
required for EMC 
compliance. Use 
SX0005 or kit 
4100-5129.