 This section describes how the IDNet on the SPS connects to addressable 
devices/detectors. 
 The guidelines governing  IDNet wiring guidelines are covered in chpt 8, IDNet 
Installation. 
 
Up to 250 IDNet initiating devices are supported on the SPS IDNet channel. The SPS 
supports both Class A (loop) and Class B(string) wiring. Class A wiring is mandatory for 
connection to more than 40 devices. 
 
Class A wiring allows IDNet appliances to communicate with the SPS even in the event 
of an open circuit somewhere in the loop. Class A wiring requires that two wires are 
routed from the SPS to each IDNet appliance, and then back again to the SPS. 
 
Class B wiring allows “T” tapping, and therefore requires less wiring distance per 
installation than Class A. Note that Class B wiring does not require end-of-line resistors, 
because each IDNet appliance communicates directly to the SPS. 
 
 
Ferrite beads are required on the SPS IDNet cables (ref Fig 7.1).  Refer to chpt 8 
IDNet Installation for the guidelines governing IDNet wiring. 
 