Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
7-14
 
 
To connect addressable devices/detectors to the SPS IDNet using Class B wiring, read the 
following instructions. 
 
1.  Under AS1670.1 Class B wiring is allowed only for a maximum of 40 
addressable devices. 
2.  A ferrite bead is required on the SPS IDNet cable. 
3.  On TB1, jumper B+ to A+, and jumper B- to A-.  
4.  Route wire (between 0.75 mm
2  
and 4 mm
2
) from the B+, B-. 
The illustration below shows Class B wiring. 
 
B+ B- SHLD
IDNet
A+
P1
3
2
1
A-
IDNet LINES TO DEVICES
(CLASS B / STYLE 4)
 
Figure 7-7. Class B Wiring 
 
 
SPS IDNet Wiring, 
Continued 
Class B Wiring 
Ferrite bead
required.