Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
7-13
 
 
To connect addressable devices/detectors to the SPS IDNet using Class A wiring, read the 
following instructions. 
 
1.  Ferrite beads are required on the SPS IDNet cables (ref Fig 7.1). 
2.  Route wire (between 0.75 mm
2
 and 4 mm
2
) from the B+, B- outputs on TB1 of 
the SPS to the appropriate inputs on a peripheral IDNet device.  
3.  Route wire from the first IDNet device to the next one. Repeat for each device. 
4.  Route wire from the last IDNet device to the A+ and A- inputs on TB1 of the 
SPS. 
 
B+ B- SHLD
IDNet
A+
P1
3
2
1
A-
IDNet
DEVICE
IDNet
DEVICE
IDNet
DEVICE
IDNet LOOP
(CLASS A / STYLE G)
 
Figure 7-6. Class A Wiring 
 
Continued on next page 
SPS IDNet Wiring, 
Continued
 
Class A Wiring 
IDNet 
DEVICE 
IDNet 
DEVICE 
IDNet 
DEVICE 
Ferrite beads
required.