To connect the IDNet card to appliances using Class B wiring, read the following 
instructions. 
 
1.  On TB1, jumper IDNetB+ to IDNet A+, and jumper IDNetB- to IDNetA-. If the 
jumper is absent, a Class A Trouble will be indicated on LED 2. 
2.  Route wire between 0.75 mm
and 4 mm
from the IDNetA+, IDNetA-, (or B+, 
B-) outputs on TB1 of the IDNet card to a junction box. Begin “T” tapping at the 
junction box. 
3.  Up to 40 devices maximum. 
4.  Sounder bases or 6 Point I/O modules in separate zones may not be wired in 
Class B. 
The illustration below shows Class B wiring. 
 
+
1
2
1
2
1
2
1
2
 
 
Figure 8-6. Class B Wiring 
 
Note:  
Maintain correct polarity on terminal connections. Do not loop wires 
under terminals. 
 
Wiring to IDNet Devices, 
Continued 
Class B Wiring 
IDNET CARD
IDNET DEVICES
0.75 mm
and 4 mm
2
FERRITE BEAD (see fig 7.1)