This section describes the messages that may appear on the 4100 display when using the 
IDNet card. Trouble messages appear on the left as titles, and possible causes are listed to 
the right in the text. 
 
There is no output voltage from the IDNet power supply. Replace the IDNet card. 
 
Appears if one or more extra devices (i.e., devices that have not been configured for the 
IDNet channel) are found on the system, or if a device is at an incorrect address. Only one 
message appears, regardless of the number of extra devices found. Viewing the trouble 
log will reveal the extra device address. 
 
There is an open on the IDNet channel. After fixing the wiring fault, a hardware reset is 
required to reset the trouble. 
 
Appears while the IDNet card is searching for earth faults on the IDNet line. When this 
message is displayed, the IDNet card cannot show any alarms or other statuses. 
 
Appears when a short is detected on the IDNet channel. This status clears automatically 
when the short circuit is removed. 
 
Appears when devices have been configured, but none of the devices are communicating 
on the channel. This message does not appear if there are no configured devices on the 
IDNet channel. 
 
Appears when a device is missing. 
 
Appears when there is a faulty device or a noisy communications channel. 
 
 
Occurs during any of these conditions: 
24 V is not present on TrueAlarm devices. 
TrueAlarm sensor bases with relay driver outputs are not properly supervised. 
Isolator devices are in isolation mode. 
 
Troubleshooting on IDNet 
Overview 
IDNet Power  
Monitor Trouble 
Extra Device 
Class A Trouble 
Earth Fault Search 
Short Circuit 
Channel Fail 
No Answer 
Bad Answer 
Output Abnormal