Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
8-11
 
 
The 4100MXP is a 4” x 5” card, similar to the IDNet, but allows the 4100U to 
communicate with a Loop of MX devices.  The firmware in the 4100U sees the 
4100MXP as an IDNet, and all the MX devices are matched to the nearest Simplex 
device. 
 
 
The main difference of 4100MXP from IDNet is that it has a nominal 40V loop supply 
voltage and is capable of supplying up to 1A of loop current. 
 
The power for this loop supply is drawn from the 24V Signal bus, which is only present 
on the PDI when an XSPS is directly attached to it. 
 
Details of the 4100MXP is provided in manuals LT0313 and LT0314. 
 
 
 
 
 
 
 
The 4100MXP 
Introduction 
Power Connection