Local mode is supported by the following: 
•  4100-3101/3104/3105 IDNet Card 
•  4100-5101/5102/5103 Expansion Power Supply NACs (including TrueAlert 
Non-Addressable SmartSync appliances) 
•  4100-5111/5112/5113 System Power Supply NACs (including TrueAlert Non-
Addressable SmartSync appliances) 
•  4100-5125/5126/5127 Remote Power Supply NACs (including TrueAlert Non-
Addressable SmartSync appliances) 
•  4100-5120/5121/5122 TrueAlert Power Supply NACs 
•  4100-1214 to -1225, 4100-1228 to –1239, 4100-1314 to -1325, 4100-1328 to –
1339, 
100 W Amplifier NACs 
•  4100-1212/1213/1226/1227/1312/1313/1326/1327 Flex 50 Amplifier NACs 
•  4009-9401 TrueAlert Addressable Controller 
•  4100-1270 Phone Controller and 4100-1272/1273 Phone NAC cards 
•  4009-9201/ 9301 IDNet NAC Extender 
•  4100-5116 Expansion Signal Card 
 
Local mode is NOT supported by, but can co-exist with, the following:
 
•  4100 Legacy cards 
•  4100-3101 to -3103 Auxiliary Relay Cards 
•  4100-6048 VESDA
 Interface Kit 
•  4100-6043/6044 RS-232/2120 Interfaces 
•  4100-1280 to -1287 LED/Switch Annunciators 
•  4100-1290 24-Point Graphic I/O Module  
•  4602-9101 SCU/ 4602-9102 RCU 
•  4603-9101 LCD Annunciator 
•  4100-1210/1211/1311 Audio Controller Board  
•  4100-6014 Network Interface Card 
•  4100-6052 DACT 
 
Bear in mind the following limitations for when local mode is in effect: 
•  If an alarm is already activated when local mode is initiated, the alarm remains 
activated in local mode. 
•  Software zones are not supported. Basic TrueAlert channels are supported. 
•  Alarm verification is not supported. All alarms are reported immediately. 
•  SMPL is not supported. 
•  TrueAlarm sensors have fixed thresholds. 
 