Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
4-6
 
 
The TICs have the following LEDs: 
 
LED1. Illuminates to indicate communication loss with the CPU. 
LED2. Illuminates when an RUI ground fault search is active. 
LED3. Illuminates when Local Mode is active. 
LED4. Illuminates to indicate an RUI Style 7 primary trouble. 
LED5. Illuminates to indicate an RUI Style 7 secondary trouble.  
 
Refer to Figure 5-1 to see which LEDs are included on which TIC. Most TICs do not 
contain all LEDs. 
 
Table 5-1 lists the specifications for all TICs. 
Table 5-1. TIC Specifications 
Electrical Specifications 
Input Voltage 
18-33 VDC 
Output Voltage 
8 V @ 1 A; 100 mV p-p ripple 
Input Current 
87 mA for all TICs.  112 mA for a local mode TIC 
connected to a local mode annunciator. 
Environmental Specifications 
Operating 
Temperature 
32
° to 120° F (0° to 49° C) 
Humidity 
10% to 93% relative humidity at 90
° F (32° C) 
 
Introduction to MINIPLEX Transponders (4100U), 
Continued
 
LEDs 
Card Specifications