Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
4-7
 
 
The rules on this page apply exclusively to MINIPLEX systems. Review each guideline 
before installing a MINIPLEX 4100U system. 
 
•  All wiring is 18 AWG (0.8231 mm
2
) (minimum) and 12 AWG (3.309 mm
2
(maximum). 
•  All wiring is supervised and power-limited. 
•  All wiring that leaves the building requires overvoltage protection. Install 
module  
inside an UL-Listed electrical box wherever wire enters or exits the building. A 
maximum of four 2081-9044 Modules may be connected to one channel. The 
2081-9044 is rated for 200 mA (maximum). 
•  AS1670 allows the loss of a maximum of 40 detectors/addressable devices to be 
caused by a single fault. 
•  For Style 4 operation:  
-  The maximum distance to any device is 2,500 feet (762 m). 
-  “T” taps are allowed. 
-  The total maximum distance (including all “T” taps) is 10,000 feet (3,048 m). 
-  Maximum allowed line-to-line capacitance (“+” to “-” terminals) is 0.58 uF. 
For  applications with shielded wire, be sure that the total capacitance from line 
to line plus   the shield to either line is no more than 0.58 uF. 
•  For Style 6 or Style 7 operation, the maximum loop distance is 2,500 feet (762 
m). “T” taps are not allowed. 
•  RUI comms are wired to remote cabinets from the CPU motherboard to one of 
the following transponder interface cards: 4100-0620 (566-093) or 4100-0625 
(566-094). 
•  Annunciators and transponder interface cards support Style 7 operation when the 
system is wired Class A. 
•  The master control panel must be a 4100U Fire Alarm Control Panel. 
•  The Style 4 RUI card supports MINIPLEX transponders and 4602/4603 serial 
annunciators on the same signaling line circuit. 
•  Up to 4 RUI cards in the 4100U Control Panel can be used for distributing 
transponder wiring in different directions or for supporting different wiring 
requirements (such as using a Style 7 RUI for serial annunciators). 
•  Up to 31 transponders can be controlled from the 4100U Control Panel, and can be 
distributed as required among the RUI cards. 
 
 
 
 
MINIPLEX System Guidelines (4100U) 
Overview 
Guidelines