Ferguson JWSH100150 Manual Do Utilizador

Página de 36
12
 WARNING
THE  HEATER  IS  NOT  INTENDED  FOR  OPERATION  AT  HIGHER 
THAN 10.5" (2.59 KPa) WATER COLUMN SUPPLY GAS PRESSURE. 
HIGHER    GAS  SUPPLY  PRESSURES  REQUIRE  SUPPLEMENTAL 
REDUCING  SERVICE  REGULATION.  EXPOSURE  TO  HIGHER 
GAS  SUPPLY  PRESSURE  MAY  CAUSE  DAMAGE  TO  THE  GAS 
CONTROLS  WHICH  COULD  RESULT  IN  FIRE  OR  EXPLOSION.  IF 
OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER 
TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE 
SUPPLY SYSTEM THE GAS VALVE MUST BE CHECKED FOR SAFE 
OPERATION.  MAKE  SURE  THAT  THE  OUTSIDE  VENTS  ON  THE 
SUPPLY  REGULATORS  AND  THE  SAFETY  VENT  VALVES  ARE 
PROTECTED  AGAINST  BLOCKAGE.  THESE  ARE  PARTS  OF  THE 
GAS SUPPLY SYSTEM, NOT THE HEATER. VENT BLOCKAGE MAY 
OCCUR DURING ICE STORMS.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM 
CONTAMINANTS  IN  THE  GAS  WAYS.  SUCH  FOULING  MAY  CAUSE 
IMPROPER OPERATION, FIRE OR EXPLOSION. 
IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY 
TINNED AND CERTIFIED FOR GAS SERVICE.
BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS 
CLEAN ON THE INSIDE.
TO  TRAP  ANY  DIRT  OR  FOREIGN  MATERIAL  IN  THE  GAS  SUPPLY 
LINE, A DIRT LEG (SOMETIMES CALLED A SEDIMENT TRAP OR DRIP 
LEG)  MUST  BE  INCORPORATED  IN  THE  PIPING  (SEE  FIGURE  13). 
THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT 
TO  FREEZING  CONDITIONS.  INSTALL  IN  ACCORDANCE  WITH 
RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO THE 
NATIONAL FUEL GAS CODE.
FIGURE 13.
CONNECTION OF GAS PIPE
1.  When connecting gas pipe to unit, apply wrench to flange only. Note:  
Do not use wrench on gas valve or gas bracket.  See Figure 14a & b.
2.  PERFORM  THE  GAS  LEAK  TEST  ANY  TIME  WORK  IS  DONE 
ON  A  GAS  SYSTEM  TO  AVOID  THE  POSSIBILITY  OF  FIRE  OR 
EXPLOSION WITH PROPERTY DAMAGE, PERSONAL INJURY OR 
LOSS OF LIFE.
FIGURE 14a. (A)JWSH100199 & (A)JWSH100250 Models Only
FIGURE 14b. (A)JWSH100150 Models Only
The Gas Leak Test is performed as follows:  Paint pipe connections upstream 
of gas control with a rich soap and water solution to test for leaks before 
operating main burner. Bubbles indicate gas leak. To stop leak, tighten pipe 
connections. After piping connections are checked, turn on main burner. With 
main burner in operation, paint pipe joints (including flanges), pilot gas tubing 
connections and control inlet and outlet with rich soap and water solution. 
Bubbles indicate gas leak. To stop leak, tighten flange screws, joints and 
pipe connections. Replace part if leak can’t be stopped.
To prevent damage, care must be taken not to apply too much torque when 
attaching gas supply pipe to gas valve inlet. 
Apply joint compounds (pipe dope) sparingly and only to the male threads of 
pipe joints. Do not apply compound to the first two threads. Use compounds 
resistant to the action of liquefied petroleum gases.