DISCONNECT  THE APPLIANCE AND  ITS  MANUAL  GAS  SHUTOFF 
VALVE  FROM  THE  GAS  SUPPLY  PIPING  SYSTEM  DURING ANY 
SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45Kpa). GAS 
SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE 
HEATER. FOR TEST PRESSURES OF 1/2 PSIG (3.45Kpa) OR LESS, THE 
APPLIANCE NEED NOT BE DISCONNECTED, BUT MUST BE ISOLATED 
FROM THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS 
SHUTOFF VALVE.
BEFORE  PLACING THE  HEATER  IN  OPERATION,  CHECK  FOR  GAS 
LEAKAGE. USE SOAP AND WATER SOLUTION OR OTHER MATERIAL 
ACCEPTABLE FOR THE PURPOSE OF  LOCATING GAS LEAKS. DO NOT 
USE MATCHES, CANDLES, FLAME OR OTHER SOURCES OF IGNITION 
FOR THIS PURPOSE.
PURGING
Gas line purging is required with new piping or systems in which air has 
entered.
 
CAUTION
PURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED IN 
THIS TYPE OF GAS SERVICE. TO AVOID RISK OF FIRE OR EXPLOSION, 
PURGE  DISCHARGE  MUST  NOT  ENTER  CONFINED AREAS  OR 
SPACES WHERE IGNITION CAN OCCUR. THE AREA MUST BE WELL 
VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED 
OR REMOVED. 
GAS METER SIZE - CITY GASES ONLY
Be sure that the gas meter has sufficient capacity to supply the full rated gas 
input of the water heater as well as the requirements of all other gas fired 
equipment supplied by the meter. If the gas meter is too small, ask the gas 
company to install a larger meter having adequate capacity.
GAS PRESSURE REGULATION
Main line gas pressure to the water heater should be between a maximum 
10.5" (2.59Kpa) W.C. (14.0"/3.45Kpa for propane) and a minimum as shown 
in Table 4: that is, for Natural Gas, 4.8" (1.18Kpa) W.C. and 8.5" (2.08Kpa) for 
Propane Gas. The inlet gas pressure must not exceed the maximum value. 
A service regulator must be installed within 10' (305 cm) of unit.
 WARNING
FAILURE TO INSTALL A PRESSURE REGULATOR WITHIN 10 FEET OF 
THE WATER HEATER CAN RESULT IN LEAKAGE OF FLUE GASES INTO 
THE SURROUNDING ROOM. SERIOUS PERSONAL INJURY OR DEATH 
COULD RESULT FROM INHALATION OF CARBON MONOXIDE GAS.
GAS VALVES
 WARNING
SHOULD  OVERHEATING  OCCUR  OR  THE  GAS  SUPPLY  FAIL  TO 
SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE 
APPLIANCE.
SYSTEM CONNECTIONS
The system installation must conform to these instructions and to the local 
code  authority  having  jurisdiction.  Good  practice  requires  that  all  heavy 
piping be supported.
THERMOMETERS (Not Supplied)
Thermometers  should  be  obtained  and  field  installed  as  shown  in  the 
installation diagrams.
Thermometers  are  installed  in  the  system  as  a  means  of  detecting  the 
temperature of the outlet water supply.
RELIEF VALVE
This heater is equipped with an approved temperature and pressure relief 
valve. ASME ratings cover pressure relief. CSA ratings cover release rate 
with temperature actuation.
FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF VALVE(S) 
MUST NOT BE REMOVED OR PLUGGED.
In  addition  to  the  appliance  relief  valve,  each  remote  storage  tank 
which  may  be  used  in  conjunction  with  this  appliance  shall  also  be 
installed with a properly sized, rated and approved temperature (ANSI) 
and  pressure  (ASME)  relief  valve(s).  This  relief  valve  shall  comply 
with the standard for relief valves for hot water supply systems. ANSI 
Z21.22-CSA 4.4.
Your  local  code  authority  may  have  other  specific  relief  valve 
requirements.
 WARNING
THE  PURPOSE  OF  A  RELIEF  VALVE  IS  TO  AVOID  EXCESSIVE 
PRESSURE OR TEMPERATURE INTO THE STEAM RANGE, WHICH 
MAY CAUSE SCALDING AT FIXTURES, TANK EXPLOSION, SYSTEM 
OR HEATER DAMAGE. NO VALVE IS TO BE PLACED BETWEEN THE 
RELIEF VALVE AND THE TANK.
A  DRAIN  LINE  MUST  BE  CONNECTED  TO  THE  RELIEF  VALVE  TO 
DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR 
WATER  DAMAGE. THIS  LINE  MUST  NOT  BE  REDUCED  FROM THE 
SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES OR 
RESTRICTIONS, NOR SHOULD IT BE LOCATED IN FREEZING AREAS. 
DO NOT THREAD OR CAP THE END OF THIS LINE. RESTRICTED OR 
BLOCKED  DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE 
AND  IS  UNSAFE. THE  DISCHARGE  LINE  SHALL  BE  INSTALLED TO 
ALLOW COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.
WATER LINE CONNECTIONS 
This manual provides detailed installation diagrams (see back section of this 
manual) for typical methods of application for the water heaters. 
The  water  heater  may  be  installed  by  itself,  or  with  a  separate  storage 
tank. 
CLOSED SYSTEM
 CAUTION
A closed system will exist if a check valve (without bypass), pressure reducing 
valve (without bypass), or a water meter (without bypass) is installed in the 
cold water line between the water heater and street main (or well). 
Excessive  pressure  may  develop  causing  premature  tank  failure  or 
intermittent  relief  valve  operation.  This  type  of  failure  is  not  covered 
by the limited warranty. An expansion tank or a similar device may be 
required in the inlet supply line between the appliance and the meter or 
valve to compensate for the thermal expansion of water under supply 
pressure.
If a water heater is installed in a closed water system, check local codes 
or contact the water supplier or local plumbing inspector on how to control 
this situation.
WATER (POTABLE) HEATING AND SPACE HEATING
1. All  piping  components  connected  to  this  unit  for  space  heating  
  applications shall be suitable for use with potable water.
2. Toxic  chemicals,  such  as  those  used  for  boiler  treatment,  shall  
 
NEVER be introduced into this system.