Honeywell XL 800 SERIES Manual Do Utilizador
Mounting/Dismounting Modules
Excel 800
EN1B-0410GE51 R0908A
14
LOCK
4
4
Fig. 14. HEX switch location
NOTE:
If the HEX switch setting is changed, the Panel
Bus I/O module will revert to its default
configuration. With L
Bus I/O module will revert to its default
configuration. With L
ON
W
ORKS
Bus I/O modules,
the HEX switch is without function.
Setting the I/O Bus Switch
►
Set the I/O Bus switch S2 of the XCL8010AU
Controller
Module depending on the modules connected to terminals
71 ─ 78 and the desired communication as follows:
71 ─ 78 and the desired communication as follows:
Table 10. I/O Bus switch settings
communication
S2 setting
terminals
L
ON
W
ORKS
Bus
only
LON 71
─ 74 L
ON
W
ORKS
Bus
75 ─ 78
L
ON
W
ORKS
Bus
11 ─ 14
L
ON
W
ORKS
Bus
Panel Bus and
L
L
ON
W
ORKS
Bus
Panel 71
─ 74 Panel Bus
75 ─ 78 Panel Bus
11 ─ 14 L
11 ─ 14 L
ON
W
ORKS
Bus
Fig. 15. S2 I/O Bus switch
L
ON
W
ORKS
Bus Topologies
The L
ON
W
ORKS
Bus is a 78-kilobit serial link that uses
transformer isolation so that the bus wiring does not have a
polarity. I.e. it is not important which of the two L
polarity. I.e. it is not important which of the two L
ON
W
ORKS
Bus terminals are connected to each wire of the twisted pair.
The L
The L
ON
W
ORKS
Bus does not need to be shielded on the
controller module side.
The L
The L
ON
W
ORKS
Bus can be wired in daisy chain, star, loop or
any combination thereof as long as the maximum wire length
requirements are met.
Configuration
The recommended configuration is a daisy chain with two bus
terminations. This layout allows for max. L
requirements are met.
Configuration
The recommended configuration is a daisy chain with two bus
terminations. This layout allows for max. L
ON
W
ORKS
Bus
lengths, and its simple structure presents the least number of
possible problems, particularly when adding on to an existing
bus.
possible problems, particularly when adding on to an existing
bus.
C-Bus Topologies
Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.)
can communicate with one another and a PC central. The C-
Bus must be connected via the individual controllers (open
ring).
NOTE:
can communicate with one another and a PC central. The C-
Bus must be connected via the individual controllers (open
ring).
NOTE:
Star connection is not allowed because
uncontrollable line reflections may occur.
uncontrollable line reflections may occur.
Mounting/Dismounting Modules
WARNING
Risk of electric shock or equipment damage!
►
Do not touch any live parts in the cabinet.
►
Disconnect the power supply before you start to install the
Excel 800 System.
More than one disconnect switch may be required to de-
energize the system.
Excel 800 System.
More than one disconnect switch may be required to de-
energize the system.
►
Do not reconnect the power supply until you have
completed the installation.
completed the installation.
NOTE:
The terminal socket of each I/O module can be
mounted and wired before inserting and locking
the corresponding electronic module.
mounted and wired before inserting and locking
the corresponding electronic module.