Honeywell XL 800 SERIES Manual Do Utilizador

Página de 36
Excel 800 
Troubleshooting 
 35 
EN1B-0410GE51 
R0908A 
Service LED of I/O Modules 
Table 43. Service LED of I/O modules 
case 
Service LED 
meaning 
remedy 
LED remains OFF after 
power-up 
If the power LED is also OFF, then 
– Defective 
device 
hardware 
–  Possible power supply problems, clock 
problems, defective processor 
► Replace hardware 
LED is lit continuously after 
first power-up 
•  L
ON
W
ORKS
 Bus I/O modules: 
– Defective 
hardware 
•  Panel Bus I/O modules: 
–  I/O module has not yet been configured 
by XCL8010AU 
–  Boot loader is active 
–  Failure during last firmware download 
– Checksum 
error 
L
ON
W
ORKS
 Bus I/O modules: 
► Replace hardware 
Panel Bus I/O modules: 
►  Set the hex address to the position configured 
with CARE 
►  Ensure that I/O Bus switch S2 of XCL8010AU is 
set to position "Panel" 
►  Check the Panel Bus wiring: 
-  Check for cable breaks 
-  Check for cable short-circuits 
-  If using separate transformers: Check ground 
connection 
►  Eliminate any mixture of Panel Bus I/Os and 
LonWorks I/Os on same wire 
►  Allow XCL8010AU to configure I/O module 
►  Unplug and replug the module 
►  If problem persists, replace hardware 
Alternating flash between 
service LED and power LED 
Panel Bus I/O modules, only: 
Download error or application checksum error. 
Boot loader is running 
►  Panel Bus I/O modules, only: 
Wait until rebooting (firmware download) has 
been completed 
LED flashes at power up, 
goes OFF, and then is lit 
continuously 
L
ON
W
ORKS
 Bus I/O modules, only:  
L
ON
W
ORKS
 Bus I/O module lacks application 
► Download application 
LED repeatedly blinks 
ON for 1 sec and 
OFF for 1 sec 
L
ON
W
ORKS
 Bus I/O modules, only:  
L
ON
W
ORKS
 Bus I/O module is unconfigured, but 
has an application 
►  Set module to configured mode 
LED remains OFF after a 
short ON duration 
I/O module is configured and running normally 
No action necessary 
LED flashes continuously in 
following pattern: 
4 x ON/OFF followed by 
pause 
Sensor failure of Analog Input Module  
(in case of L
ON
W
ORKS
 Bus I/O modules, this 
behavior can occur only if the appropriate NV 
has been bound) 
►  Check sensor or connection 
►  Check sensor configuration 
LED flashes continuously in 
following pattern: 
5 x ON/OFF followed by 
pause 
L
ON
W
ORKS
 Bus I/O modules, only: L
ON
W
ORKS
 
I/O Bus module has received the wink 
command from network, physical outputs are 
unaffected 
No action necessary 
LED flashes continuously in 
following pattern: 
6 x ON/OFF followed by 
pause 
Boot loader problem or hardware defect  
► Replace hardware 
10 
LED flashes continuously in 
following pattern: 
7 x ON/OFF followed by 
pause 
Communications failure 
►  Check bus wiring 
►  Ensure that I/O Bus switch S2 of XCL8010AU is 
set to correct position 
►  Ensure that L
ON
W
ORKS
 Bus I/O modules and 
Panel Bus I/O modules are not sharing same 
bus 
►  In case of Panel Bus I/O modules, only: 
Check for incorrect HEX addresses (2 Panel Bus 
I/O modules using same HEX address) 
►  In case of L
ON
W
ORKS
 Bus I/O modules, only: 
Check heartbeat