Honeywell XL 800 SERIES Manual Do Utilizador

Página de 36
 
Excel 800 
EN1B-0410GE51 R0908A 
 
34
I/O Modules Troubleshooting 
► 
Check if the power supply voltage level is OK and that there is no high voltage (> 24 VAC or > 40 VDC) connected to the 
inputs/outputs of the XF821AU, XFL821AU, XF822AU, XFL822AU, XFR822AU, XFLR822AU, XF823AU, and XFL823AU I/O 
modules. 
► 
Replace the problem I/O module with another module of the same kind. 
–  If the problem persists, this is an indication that the problem is caused by the application or incorrect wiring. 
–  If the problem is solved, this is an indication that the I/O module was defective. 
 
For troubleshooting purposes on all I/O modules the following features can be used: 
• Power 
LED 
• Service 
LED 
• Service 
button 
In addition, a module-specific troubleshooting may be necessary. 
 
Power LED of I/O Modules 
Table 42. Power LED of I/O modules 
case 
power LED 
meaning 
remedy 
1 ON 
I/O module is powered 
No action necessary 
2 OFF 
No power 
► 
Check power supply 
3 Flashing 
continuously 
If the I/O module’s service LED is likewise 
flashing, the I/O module is in the boot mode 
► 
Wait until rebooting (firmware 
download) has been completed