Honeywell XL 800 SERIES Manual Do Utilizador

Página de 36
Excel 800 
Troubleshooting 
 33 
EN1B-0410GE51 
R0908A 
Table 39. XCL8010AU L
ON
W
ORKS 
service LED 
case 
When can it occur? 
meaning 
remedy 
Anytime 
Node is configured and running normally 
No action necessary 
Power up of controller 
Bad node hardware 
► 
Replace hardware 
Power up of controller 
Bad node hardware 
► 
Replace hardware 
Power up / reset 
Node lacks application.  
May be caused by neuron chip firmware when 
a mismatch occurs on application checksum 
► 
Using EXCELON, set module to 
“configured online” 
► 
If problem persists, the MIP software 
on LW interface has been erased due 
to wrong setting performed using 
ECHELON tool:  
Replace hardware 
Anytime 
Watchdog timer resets occurring.  
Possible corrupt EEPROM and bootstrap 
mode 
► 
Download firmware 
Anytime 
Node is unconfigured but has an application 
► 
Proceed with commissioning 
 
C-Bus Tx and Rx LEDs 
Table 40. XCL8010AU C-Bus Tx and Rx LEDs 
case 
C-Bus LEDs 
meaning 
remedy 
If the C-bus is functioning properly, then the 
XCL8010AU is functioning properly 
No action necessary 

 
Both LEDs are flashing 
If the C-bus is not functioning properly, then 
the termination can be wrong 
► 
Check C-bus termination switch S1 
(location: see Fig. 4 on page 7) 
Both LEDs are OFF 
No C-bus communication 
► 
Check C-bus settings 
Both LEDs are flashing 
synchronously 
No C-bus communication 
► 
Check C-bus wiring 
 
HMI Tx and Rx LEDs 
Table 41. XCL8010AU HMI Tx and Rx LEDs 
case 
HMI LEDs 
meaning 
remedy 
Both LEDs are flashing 
If the HMI Interface is functioning properly, 
then the XCL8010AU is functioning properly 
No action necessary 
Both LEDs are OFF 
No HMI Interface communication 
► 
Check HMI Interface connection and 
proper earthing of connected 
hardware