Output Terminal Configuration
The inverter provides configuration for logic (discrete) and analog outputs, shown in the 
table below.
The output logic convention is programmable for terminals [11], [12], and the alarm 
relay terminals. The open-collector output terminals [11] and [12] default to normally 
open (active low), but you can select normally closed (active high) for these terminals in 
order to invert the sense of the logic. You can invert the logical sense of the alarm relay 
output as well.
“C” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
C021 Terminal [11] function
10 programmable functions 
available for logic (discrete) 
outputs (see next section)
01
[FA1]
01
[FA1]
OUT-TM 11    FA1
C022 Terminal [12] function
00
[RUN]
00
[RUN]
OUT-TM 12    RUN
C026 Alarm relay terminal 
function
05
[AL]
05
[AL]
OUT-TM RY    AL
C028 [AM] signal selection
Two available functions:
00... Actual motor speed
01... Motor current
(see after next section)
00
output
freq.
00
output
freq.
AM-KIND        F
“C” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
C031 Terminal [11] active 
state
Select logic convention, two 
option codes:
00... normally open (NO)
01... normally closed (NC)
00
00
O/C-11        NO
C032 Terminal [12] active 
state
Select logic convention, two 
option codes:
00... normally open (NO)
01... normally closed (NC)
00
00
O/C-12        NO
C036 Alarm relay active  state Select logic convention, two 
option codes:
00... normally open (NO)
01... normally closed (NC)
01
01
O/C-RY        NC