“C” Group: Intelligent Terminal Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–48
Output Function Summary Table – This table shows all ten functions for the logical 
outputs (terminals [11], [12]) at a glance. Detailed descriptions of these functions, 
related parameters and settings, and example wiring diagrams are in 
.
Output Function Summary Table
Option
Code
Terminal 
Symbol
Function Name
Description
00
RUN
Run Signal
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
01
FA1
Frequency Arrival 
Type 1 – Constant 
Speed
ON
when output to motor is at the set frequency
OFF
when output to motor is OFF, or in any accelera-
tion or deceleration ramp
02
FA2
Frequency Arrival 
Type 2 – Over-
frequency
ON
when output to motor is at or above the set 
frequency, even if in accel. or decel. ramps
OFF
when output to motor is OFF, or at a level below 
the set frequency
03
OL
Overload Advance 
Notice Signal
ON
when output current is more than the set thresh-
old for the overload signal
OFF
when output current is less than the set threshold 
for the overload signal
04
OD
Output Deviation for 
PID Control
ON
when PID error is more than the set threshold for 
the deviation signal
OFF
when PID error is less than the set threshold for 
the deviation signal
05
AL
Alarm Signal
ON
when an alarm signal has occurred and has not 
been cleared
OFF
when no alarm has occurred since the last 
clearing of alarm(s)
06
Dc
Analog Input
Disconnect Detect
ON
when the [O] input value < B082 setting (signal 
loss detected), or the [OI] input current < 4mA
OFF
when no signal loss is detected
07
FBV
PID Second Stage 
Output
ON
Transitions to ON when the inverter is in RUN 
Mode and the PID Process Variable (PV) is less 
than the Feedback Low Limit (C053)
OFF
Transitions to OFF the PID Feedback Value (PV) 
exceeds the PID High Limit (C052), and transi-
tions to OFF when the inverter goes from Run 
Mode to Stop Mode.
08
NDc
Network Detection 
Signal
ON
when the communications watchdog timer 
(period specified by C077) has timed out
OFF
when the communications watchdog timer is 
satisfied by regular communications activity