Analog Function Summary Table – This table shows both functions for the analog 
voltage output [AM] terminal, configured by C028. More information on using and 
calibrating the [AM] output terminal is in 
.
Output Function Adjustment Parameters
The following parameters work in 
conjunction with the intelligent output 
function, when configured. The overload 
level parameter (C041) sets the motor 
current level at which the overload signal 
[OL] turns ON. The range of settings is 
from 0% to 200% of the rated current for 
the inverter. This function is for generating 
an early warning logic output, without 
causing either a trip event or a restriction 
of the motor current (those effects are 
available on other functions).
The frequency arrival signal, [FA1] or 
[FA2], is intended to indicate when the 
inverter output has reached (arrived at) the 
target frequency. You can adjust the timing 
of the leading and trailing edges of the 
signal via two parameters specific to accel-
eration and deceleration ramps, C042 and 
C043.
09
LOG
Logic Output 
Function
ON
when the Boolean operation specified by C143 
has a logical “1” result
OFF
when the Boolean operation specified by C143 
has a logical “0” result
Output Function Summary Table
Option
Code
Terminal 
Symbol
Function Name
Description
Analog Function Summary Table
Option
Code
Function Name
Description
Range
00
Analog Frequency 
Monitor
Actual motor speed
0 to max. 
frequency in Hz
01
Analog Current Output 
Monitor
Motor current (% of maximum rated 
output current)
0 to 200%
Motor current
Overload 
signal
t
t
0
1
0
C041
Output
frequency
Arrival 
signal
t
t
0
1
0
C042
C043