“D” Group: Monitoring Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–6
“D” Group: Monitoring Functions
You can access important system parameter values with the “D” Group monitoring 
functions, whether the inverter is in Run Mode or Stop Mode. After selecting the 
function code number for the parameter you want to monitor, press the Function key 
once to show the value on the display. In functions D005 and D006, the intelligent termi-
nals use individual segments of the display to show ON/OFF status.
If the inverter display is set to monitor a parameter and powerdown occurs, the inverter 
stores the present monitor function setting. For your convenience, the display automati-
cally returns to the previously monitored parameter upon the next powerup.
“D” Function
Run 
Mode 
Edit
Units
Func.
Code
Name /
SRW Display
Description
D001 Output frequency 
monitor
Real-time display of output 
frequency to motor, from
0.0 to 400.0 Hz
Hz
FM     0000.00Hz
D002 Output current monitor
Filtered display of output current 
to motor (100 ms internal filter 
time constant), range is
0 to 200% of inverter rated current
A
Iout     0000.0A
D003 Rotation direction 
monitor
Three different indications:
“F”..... Forward
“o” .. Stop
“r”..... Reverse
Dir         STOP
D004 Process variable (PV), 
PID feedback monitor
Displays the scaled PID process 
variable (feedback) value (A075 is 
scale factor),
0.00 to 99.99, 100.0 to 999.9,
1000. to 9999., 1000 to 999,
and 10000 to 99900
% times 
constant
FB     00000.00%
D005 Intelligent input 
terminal status
Displays the state of the intelligent 
input terminals:
IN-TM      LLLLL
D006 Intelligent output 
terminal status
Displays the state of the intelligent 
output terminals:
OUT-TM       LLL
ON
OFF
1
2
3
4
5
Terminal numbers
ON
OFF
11
12
Terminal numbers
AL