Hitachi L200 Manual Do Utilizador

Página de 280
L200 Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–7
Trip Event and History Monitoring
The trip event and history monitoring feature lets you cycle through related information 
using the keypad. See 
 for 
more details.
D007 Scaled output frequency 
monitor
Displays the output frequency 
scaled by the constant in B086. 
Decimal point indicates range:
XX.XX   0.00 to 99.99
XXX.X   100.0 to 999.9
XXXX.   1000. to 9999.
XXXX     1000 to 9999 (x10=
10000 to 99999)
Hz times 
constant
F-Cnv   00000.00
D013 Output voltage monitor
Voltage of output to motor,
range is 0.0 to 600.0V
V
Vout      00000V
D016 Cumulative operation 
RUN time monitor
Displays total time the inverter has 
been in RUN mode in hours.
Range is 0 to 9999 /
1000 to 9999 /
Γ100 to Γ999 (10,000 to 99,900)
hours
RUN    0000000hr
D017 Cumulative power-on 
time monitor
Displays total time the inverter has 
been in RUN mode in hours.
Range is 0 to 9999 /
1000 to 9999 /
Γ100 to Γ999 (10,000 to 99,900)
hours
ON     0000000hr
“D” Function
Run 
Mode 
Edit
Units
Func.
Code
Name /
SRW Display
Description
“D” Function
Run 
Mode 
Edit
Units
Func.
Code
Name /
SRW Display
Description
D080 Trip counter
Number of trip events,
range is 0. to 9999
events
ERR CNT    00000
D081 Trip monitor 1
Displays trip event informa-
tion:
Error code
Output freq. at trip point
Motor current at trip point
DC bus voltage at trip point
Cumulative inverter opera-
tion time at trip point
Cumulative power-ON time 
at trip point
ERR 1   ########
D082 Trip monitor 2
ERR 2   ########
D083 Trip monitor 3
ERR 3   ########