Product Specification Sheet
00815-0100-4810, Rev AA
June 2005
3
Functional Specifications
The pressure instrument shall have the 
capability to be supplied as mounted directly 
on the COP primary when the process 
temperature is less than 450°F (232°C).
Differential pressure instruments shall be 
capacitance technology-based.
The pressure instrument sensor shall be 
hermetically sealed from the external 
environment.
The pressure instrument shall have built-in 
transient protection.
Communication Specifications
Communication with the flowmeter can occur 
via a hand-held device.
Digital communication with the flowmeter shall 
be via open protocols (e.g. HART, 
FOUNDATION
 Fieldbus). Proprietary 
protocols are not permitted.
The flowmeter shall allow field upgrading of 
communication protocols and the addition of 
advanced instrument software functions 
without changing the pressure sensor.
Software Specifications
The flowmeter shall contain user definable low 
flow cut-off functionality.
The pressure instrument shall be able to fully 
communicate with a Microsoft
®
 Windows
®
 
based instrument management software via 
an open communication protocol.
It shall be possible to store last calibration date 
and next calibration due date in the pressure 
instrument memory using a hand held 
configurator. This information should be 
available on Windows-based instrument 
management software.
All instruments shall retain original factory 
calibration settings in a permanent memory. It 
shall be possible to recall this calibration using 
a hand-held communicator.
LCD Specifications
The instrument indicator shall be LCD type. It 
shall display the numeric value and also have 
a 0-100% scale bar graph corresponding to 
the analog output. It shall be possible to 
configure the indicator to display more than 
one parameter (pressure, scaled output); in 
this case the display will toggle / scroll to show 
all selected parameters. The indicator will 
display all alarms and alerts.
Volumetric Output Flowmeters
A volumetric measurement is ideal for liquid fluid 
types.
When the COP is integrated with a differential 
pressure instrument for volumetric output, the 
flowmeter shall perform as follows:
Within ± 0.75% to ± 0.95% of flow rate, 
dependant on beta size.
The vendor shall make independent testing 
documentation available demonstrating this 
performance.
Functional Specifications
Pressure instrument hardware / software 
failure alarm shall be selectable as high, low, 
or any user-defined value.
The flowmeter shall have the ability to detect 
impulse line plugging or should allow field 
upgrading to include this by the addition of an 
electronics card.
Software Specifications
The flowmeter shall allow the digital output of 
the pressure instrument to be scaled to any 
user-defined unit (e.g 0-200 m
3
/hr, 0-9000 
gallons/min).
The flowmeter shall allow custom 
user-entered digital alerts for both high and 
low values for the pressure reading. This 
digital alert will not affect the analog output.
Flowmeters for custody transfer will have 
hardware and software write protect security. 
Hardware security will override software.
LCD Specifications
It shall be possible to remote mount 
electronics with a display up to 100 ft (30 m) 
from the pressure sensor. These electronics 
will allow full configuration of the instrument 
via a hand-held communicator.