LDVR Series Direct Vent Gas Fireplace
10007317
Top of Unit to Ceiling ............................. 36” (914mm)
Appliance
 
Top ....................................................... 0” (0 mm)
 
Bottom .................................................. 0” (0 mm)
 
Side ...................................................... 0” (0 mm)
 
Back ..................................................... 0” (0 mm)
Venting
Concentric sections of DV Vent
 
Top, bottom & sides ........................... 1” (25 mm)
Rear Vent Applications:
 
Top ..................................................... 2” (50 mm) 
 
Sides and Bottom ............................... 1” (25 mm)
A hearth is not mandatory but is recommended for  
aesthetic purposes.  We recommend a noncombustible 
hearth which projects out 12” (305mm) or more from 
the front of the fireplace.
Cold climate installation recommendation:  
When installing this unit against a 
non-insulated exterior wall or chase, 
it is mandatory that the outer walls 
be insulated to conform to applicable 
insulation codes.  
Hearth
Mantels
The height that a combustible mantel is fitted above the 
fireplace is dependent on the depth of the mantel. This 
also applies to the distance between the mantel leg (if 
fitted) and the fireplace.
For the correct mounting height and widths refer to 
Figs. 3a and  3b, and the following Mantel Charts.
The fitting of a bay window trim kit does not effect 
the distances and reference points referred to in the 
diagram and chart.
Noncombustible mantels and legs may be installed at 
any height and width around the appliance. 
When using paint or lacquer to finish the mantel, such 
paint or lacquer must be heat resistant to prevent 
discoloration.
Clearance to Combustibles
CFM170
J
F
G
H
I
Mantel
Leg
CFM164a
Mantel Leg Chart
06/22/01   sta
Black 
Surround 
Face
CFM170
DV Builder Front 
View
O
N
M
L
K
Side of 
Combustion Chamber
CFM164a
 
 
Mantel 
  Mantel Leg FromSide
  Ref. 
Leg Depth  Ref.  of Comb. Opening
  F 
10” (254mm) 
11¹⁄₂” (292 mm)
  G 
8” (203mm) 
9¹⁄₂” (241 mm)
  H 
6” (152mm) 
7¹⁄₂” (191 mm)
  I 
4” (101mm) 
5¹⁄₂” (140 mm)
  J 
2” (50mm) 
3¹⁄₂” (89 mm)
Fig. 3b  Combustible mantel leg minimum installation.
CFM146
A B C D E
V
W
X
Y
Z
Fireplace
CFM146
DV Mantel Chart
7/5/01   sta
Top Louvre As-
sembly
Top of Combustion 
Chamber
Mantel Chart
   
Mantel Shelf 
 
Mantel from Top 
 Ref.  or Breast Plate  Ref. 
of Combustion Chamber
   
Depth 
  36/39/43 LDVR 
33LDVR
  V 
10” (254 mm)  A  17” (432 mm)  16¹⁄₂” (419 mm)
  W 
8” (203 mm) 
B  15” (381 mm)  14¹⁄₂” (368 mm)
  X 
6” (152 mm) 
C  13” (330 mm)  12¹⁄₂” (318 mm)
  Y 
4” (101 mm) 
D  11” (279 mm)  10¹⁄₂” (267 mm)
  Z 
2” (50 mm) 
9” (229 mm)  8¹⁄₂” (216 mm) 
Fig. 3a  Combustible mantel minimum installation.
This  appliance  may  be  installed  in  an  aftermarket 
permanently  located,  manufactured  home  or  mobile 
home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated 
on the rating plate. This appliance is not convertible for 
use with other gases, unless a certified kit is used. 
The  LDVR  has  been  approved  for  mobile  home 
installations.